DISASSEMBLY PROCEDURE
10
1. Removing the electrical parts
(1) Remove the 2 screws and the electrical parts cover.
(See Photo 1.)
●
Indoor controller board
●
Transformer
●
Run capacitor
●
Fuse (3.15A)
●
Terminal block
(See Photo 2.)
OPERATING PROCEDURE
PHOTOS
2. Removing the indoor coil thermistor(RT12)
(1) Remove the electrical parts cover.
(See Photo 1.)
(2) Remove the 2 screws and the service panel.
(See Photo 1.)
(3) Remove the thermistor (RT12) from the holder.
(See Photo 3.)
(4) Disconnect the connector (CN112) from the indoor
controller board and pull the lead wire of thermistor
(RT12) out.
Drain pan
Electrical parts cover
Service panel
Front panel
Set screws
(for drain pan)
Fuse
Set screws
Terminal block
Transformer
Run capacitor
Thermistor
(RT12)
Photo 2.