 88 

-

 '15 • PAC-T-236

Press         or         button.

Make sure which do you want to set, "     FUNCTION     " 
(remote control function) or "I/U FUNCTION     " (indoor unit 
function).

Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table.

Function No.
Remote controller 

function02
Remote controller 

function06
Remote controller 

function07
Remote controller 

function13

Remote controller 

function15

Default

Model

Indoor unit with only one of air flow setting
Heat pump unit

Exclusive cooling unit

"Auto-RUN" mode selectable indoor unit.
Indoor unit without "Auto-RUN" mode
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting

Item

[Flow of function setting]

Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit. 

But only master indoor unit is received the setting change of indoor unit function “05 EXTERNAL INPUT” and “06 PERMISSION /

PROHIBISHION”.

Indoor unit No. are indicated only when 
plural indoor units are connected.

01

02

Validate setting of ESP:External Static Pressure

Invalidate setting of ESP

Automatical operation is impossible

Temperature setting button is not working

02

03

03

04

04

05

05

06

06

07

07

08

09

08

10

09

11

10

12

11

13

12

13

14

14

15

16

15

17

18

19

Consult the technical data etc. for each control details

Finalize : Press “

” (SET) button.

Reset

: Press “

” (RESET) button.

Select : Press                 button.
End

: Press ON/OFF  button.

It is possible to finish above setting on the way, 
and unfinished change of setting is unavailable.

” : Initial settings

” : Automatic criterion

How to set function

2.

1.

3.

4.

5.

It is possible to finish by pressing  ON/OFF  button on the way, but unfinished change of setting is 

unavailable.
During setting, if you press              (RESET) button, you return to the previous screen.
Setting is memorized in the control and it is saved independently of power failure.

Permission/prohibition control of operation will be valid.

Record and keep the

setting

The functional setting

Stop air-conditioner and press

          (SET) +           (MODE) buttons

at the same time for over three seconds.

Function

setting

Function

setting

Mode button is not working

On/Off button is not working

Fan speed button is not working

Louver button is not working

Timer button is not working

Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro2.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0˚C increase in temperature.

If you change the range of set temperature, the indication of set temperature 

will vary following the control.

If you change the range of set temperature, the indication of set temperature

will not vary following the control, and keep the set temperature.

If you change the remote controller function "14                        ", 

you must change the indoor function "04                      " accordingly. 

You can select the louver stop position in the four.

The louver can stop at any position.

In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote controller can be indicated.)

Heating preparation indication should not be indicated.

Temperature indication is by degree C
Temperature indication is by degree F

To set other indoor unit, press

AIRCON

 NO.  button, which 

allows you to go back to the indoor 
unit selection screen 
(for example: I/U 000     ).

ON/OFF  button

(finished)

The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then the indoor unit will be stopped by 
compulsion after 24 hours.
If you change the indoor function "04                           ",
you must change the remote controller function "14                         " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.

With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately. 

To be reset for pro3.0˚C increase in temperature during heating.
To be reset for pro2.0˚C increase in temperature during heating.
To be reset for pro1.0˚C increase in temperature during heating.

To be reset pro2.0˚C increase in return air temperature of indoor unit.
To be reset pro1.5˚C increase in return air temperature of indoor unit.
To be reset pro1.0˚C increase in return air temperature of indoor unit.

To be reset producing -1.0˚C increase in return air temperature of indoor unit.
To be reset producing -1.5˚C increase in return air temperature of indoor unit.
To be reset producing -2.0˚C increase in return air temperature of indoor unit.

When heating thermostat is OFF, fan speed is low speed.
When heating thermostat is OFF, fan speed is set speed.

When heating thermostat is OFF, fan speed is operated intermittently.
When heating thermostat is OFF, the fan is stopped.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set "FAN OFF" when the indoor unit's thermistor is working.

Drain pump is run during cooling and dry.
Drain pump is run during cooling, dry and heating.
Drain pump is run during cooling, dry, heating and fan.
Drain pump is run during cooling, dry and fan.

After cooling is stopped or cooling thermostat is OFF, the fan does not perform extra operation.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for half an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for six hours.

After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for six hours.

During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after five minutes' OFF.

Connected “OA Processing” type indoor unit, and is automatically defined.

Working only with the Single split series.
To control frost prevention, the indoor fan tap is raised. 

Change of indoor heat exchanger temperature to start frost prevention control.

How to check the current setting

When you select  from "No. and funcion" and press set button by the previous operation,  the "Setting" displayed first is the current 
setting.
(But, if you select "ALL UNIT      ", the setting of the lowest number indoor unit is displayed.)

Stop air-conditioner and press              (SET)              (MODE) 
buttons at the same time for over three seconds, and the 
"FUNCTION SET      " will be displayed.

Press              (SET) button.

Selecct "     FUNCTION      "  (remote control function) or "I/U 
FUNCTION     " (indoor unit function).

Operation message
Function description:      , 
setting description:

Function No.

Fixing button

Finishing button

7

2

1

6

Starting button

Previous screen button

Indoor unit selection button

Start

: Stop air-conditioner and press “

” (SET) and

” (MODE) buttons at the same time for over three seconds.

(Remote controller function)

(Indoor unit function)

In case of Single split series, by connecting ventilation device to CNT of the 

indoor printed circuit board (in case of VRF series, by connecting it to CND of the

indoor printed circuit board),  the operation of ventilation device is linked with the 

operation of indoor unit.

In case of Single split series, by connecting ventilation device to CNT of the indoor printed 

circuit board (in case of VRF series, by connecting it to CND of the indoor printed circuit 

board),  you can operate /stop the ventilation device independently by

    (VENT) button.

Press              (SET) button.

6.

"DATA LOADING" (Indication with blinking)

Display is changed to "01                       ".

7.

"DATA LOADING" (Blinking for 2 to 23 seconds to read the data)

(1)

(2)

(3)

Press              (SET) button.

On the occasion of remote control function selection

On the occasion of indoor unit function selection

Press         or         button.
"No. and function"are indicated by turns on the remote control 
function table, then you can select from them.
(For example)

Press         or         button.
Select the setting.

Press         or         button.

Select the setting.

The current setting of selected function is indicated.
(for example) "AUTO RUN ON"       If "02 AUTO RUN SET" is 
selected

Press              (SET) button.

Press              (SET) button.

Press         or         button.

Press         or         button.

Select the number of the indoor unit you are to set
If you select "ALL UNIT      ", you can set the same setting with 
all unites.

Press              (SET) 
"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, Set as the 
same procedure if you want to set continuously ,and if to 
finish, go to 7.

Press   ON/OFF   button.

Setting is finished.

Indication is changed to "02 FAN SPEED SET".
Go to      .

[Note]

If plural indoor units are connected to a remote control, 
the indication is "I/U 000" (blinking)       The lowest number of 
the indoor unit connected is indicated.

"No. and function" are indicated by turns on the indoor unit function 
table, then you can select from them.
(For example)

The current setting of selected function is indicated.
(For example) "STANDARD"       If "02 FAN SPEED SET" is 
selected.

Press              (SET) button.

"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, set as the same 
procedure if you want to set continuously , and if to finish, go to 7.

Setting

Function No.
Function

When plural indoor units are connected to a remote control, press 
the   AIRCON NO.  button, which allows you to go back to the 
indoor unit selection screen. (example "I/U 000     ")

The initial function setting for typical using is performed automatically by the indoor unit connected, when remote 
controller and indoor unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “

”, set your desired setting as for the selected item.

The procedure of functional setting is shown as the following diagram.

Function No.
Function

Setting

If you input signal into CNT of the indoor printed circuit board from external, the

indoor unit will be operated independently according to the input from external.

If you input into CNT of the indoor printed circuit board from external, all units which 

connect to the same remote controller are operated according to the input from external.

16

17

Airflow of fan becomes the three speed of         -        -        or         -        -        -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan is fixed at one speed.

Note2: Fan setting of "HIGH SPEED"

Initial function setting of some indoor unit is "HIGH SPEED".

UH - Hi 

UH - Me

UH - Hi - Me 

STANDARD

HIGH

SPEED1, 2

FAN

SPEED

SET

Hi - Lo

Hi - Me

-

-

-

-

-

-

-

Hi - Me - Lo

UH - UH - Hi - Me

UH - Hi - Me - Lo

Indoor unit air flow setting

Fan tap

PJA012D730

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for RC-EX1A

Page 1: ...5 15 PAC T 236 B PJZ012D077 1 9 3 Installation of wired remote control Option 1 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 2: ...uld be given to a new owner WARNING Ask a professional contractor to carry out installation work according to the installation manual Improper installation work may result in electric shocks fire or break down Shut OFF the main power source before starting electrical work Otherwise it could result in electric shocks break down or malfunction Do not install the unit in appropriate environment or wh...

Page 3: ...cation equipment could disrupt medical activities video broadcasting or cause noise interference CAUTION Do not install the remote control at following places It could cause break down or deformation of remote control 1 Where it is exposed to direct sunlight 2 Near the equipment to generate heat 3 Where the surface is not flat Do not leave the remote control with its upper case removed When the up...

Page 4: ... control installation procedure Determine where to install the remote control Installation Using a switch box Installed directly on a wall Wiring direction Backward Upper center Upper left Cautions for selecting installation place 1 Installation surface must be flat and sufficiently strong R C case must not be deformed 2 Where the R C can detect room temperatures accurately This is a must when det...

Page 5: ...ensions Viewed from front Take care to protect the removed upper case from moisture or dust PCB side Viewed from rear To remove the upper case from the bottom cases of R C Insert the tip of flat head screwdriver or the like in the recess at the lower part of R C and twist it lightly to remove Connect wires from X and Y terminals of R C to X and Y terminals of indoor unit R C wires X Y have no pola...

Page 6: ...wiring When the wiring is taken out from the upper center or upper left of R C Cut out the thin wall sections on the cases for the size of wire Upper center Upper left Upper case Bottom case When taking the wiring out from the upper center open a hole before separating the upper and bottom cases This will reduce risk of damaging the PCB and facilitate subsequent work When taking the wiring out fro...

Page 7: ...f R C can be used at the maximum for 1 indoor unit or 1 group One is main R C and the other is sub R C Operating range is different depending on the main or sub R C R C function Main Sub Run Stop setting temperature fan speed and flap direction operations High power and energy saving operations Energy saving setting R C sensor Test run menu operation Room temperature range setting Indoor unit sett...

Page 8: ... installation test run and maintenance are used The administrator password at factory default is 0000 This setting can be changed Refer to User s Manual When the administrator password is forgotten it can be initialized if the High power and the Energy saving buttons are pushed simultaneously for 5 seconds on the administrator password input screen Service password is 9999 which cannot be changed ...

Page 9: ... lower case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control terminal block Connect the terminal of rem with the terminal of indoor u X and Y are no polarity Wiring route is as shown in depending on the pulling ou The wiring inside the remote The sheath should be peele The peeling off length of...

Page 10: ...emote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote control case should be within 0 3mm2 recommended to 0 5mm2 The sheath should be peeled off inside the remote control case The peeling off length of each wire is as below Pulling out from upper left Pulling o...

Page 11: ... FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the fixed upper limit value displayed for two ...

Page 12: ...rdingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master remote control can be indicated Heating preparation indication should not be indicated Temperature indication is by degree C Temperature indication is by degree F ON OFF button finished Start Stop air co...

Page 13: ...emperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF fan speed is low speed When hea...

Page 14: ... the lowest number indoor unit is displayed Stop air conditioner and press SET MODE buttons at the same time for over three seconds and the FUNCTION SET will be displayed Press SET button Selecct FUNCTION remote control function or I U FUNCTION indoor unit function Operation message Function description setting description Function No Fixing button Finishing button 7 2 1 6 Starting button Previous...

Reviews: