78
Function setting No.
Function setting
No.
Description
Remarks
001
High pressure operation data [× 0.1 MPa]
Data of last hot water storage operation
002
Low pressure operation data [× 0.1 MPa]
003
Outlet hot water temperature operation data [× 0.1ºC]
004
Outdoor air temperature during operation [× 0.1ºC]
005
Total compressor operation time [× 10 h]
006
Outlet hot water temperature [× 0.1ºC]
Current values
007
Inlet water temperature [× 0.1ºC]
008
High pressure [× 0.1 MPa]
009
Low pressure [× 0.1 MPa]
010
Discharge refrigerant temperature [× 0.1ºC]
011
Suction refrigerant temperature [× 0.1ºC]
012
Operating frequency [× 0.1 Hz]
013
Flow velocity sensor [× 0.1 L/min]
016
Secondary side outlet water temperature [× 0.1ºC]
017
Secondary side flow velocity sensor [× 0.1 L/min]
018
Secondary side pump output [%]
Example) No. 001
Remote control display: 38
Actual value: 3.8 MPa
WT08219X05.book 78 ページ 2018年10月1日 月曜日 午後7時47分
Summary of Contents for QAHV
Page 83: ......