[6] Secondary side control system
When employing an indirect heat exchanger system using a separately sold Q-1SCK, be careful with regard to the
following points.
Install the Q-1SCK (flow sensor and temperature sensor) in the secondary side circuit as shown below to perform
control.
(1) Notes on configuring and selecting components
1
Points to note for secondary side water piping
I Details on components in the unit heating circuit
* For details, refer to page 11.
II Details on components in heat exchanger heating circuit
Schematic Piping Diagram and Piping System Components for secondary circuit
T
I Unit heating circuit
II Secondary side circuit
III Hot water supply circuit
Temperature sensor
Flow sensor
No.
Component
Application
Remarks and notes on selecting and installing components
1
Flow sensor
(Optional parts)
Measures and controls
the secondary side flow
rate.
Be sure to install this component between the downstream of the flow rate
adjustment device and the heat exchanger.
2
Temperature
sensor
(Optional parts)
Measures and controls
the secondary side
outlet hot water
temperature.
Install this component at the outlet of the heat exchanger.
3
Plate heat
exchanger
Exchanges heat
between hot water
output from the unit and
water input from the
tank.
Select a heat exchanger that is appropriate for the capacity.
4
Pump + Flow
rate adjustment
device
Outputs hot water from
the secondary side and
adjusts the flow rate.
Select a pump and flow rate adjustment device that are suitable for the system.
Install them at the lower outlet of the tank.
5
Water piping
Water flow channel
Be sure to perform insulation work.
Select pipes that allow for easy air bleeding.
6
Anti-freeze
heater
Prevents pipe damage
due to freezing of the
water circuit.
This component needs to be installed in a location where an ambient
temperature may fall to 0
˚
C or less.
7
Union joint
Improves the workability
of replacing equipment.
Install these components in the two places of the chilled water passage section
and the high temperature water passage section to enable replacement.
䐣 䐤
䐣 䐤
䐟
T
䐠
䐥
䐬
䐦
䐨
䐩
䐧
䐪
䐡
P
䐢
䐫
䐭
䐥
䐬
䐦
P
䐪
䐩
P
From heat pump unit
To heat pump unit
From storage tank
To storage tank