- 60 -
(6)-3 Rule of setting address
AG-150A
GB-50ADA
000, 201 ~ 250
10
1
100
0,2
0~5
0~9
PAC-YG50ECA
000, 201 ~ 250
10
1
100
0,2
0~5
0~9
BAC-HD150
000, 201 ~ 250
10
1
100
0,2
0~5
0~9
Settings are made on the initial screen of AG-150A.
Settings are made with setting tool of BM ADAPTER.
Unit
PWFY unit
Standard indoor unit
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
Note
Example
The address of outdoor unit + 1
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
System remote
controller
ON/OFF remote
controller
000, 201 ~ 250
000, 201 ~ 250
Local remote controller
System controller
The address of main remote cont 50
The address automatically becomes "200" if it is set
as "00"
LMAP02-E
201 ~ 250
1
1
Fixed
Fixed
Group remote
controller
201 ~ 250
The smallest group No. to be m 200
2
Fixed
2
Fixed
Outdoor unit
BC controller
(Main)/WCB
53 ~ 99, 100
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
BC controller
(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant
50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
(Note1)
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
10
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
10
1
10
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
10
0 1
2
3
4
5
6
7
8
9
1
0 1
2
3
4
5
6
7
8
9
10
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
10
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10
1
100
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
10
1
100
10
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.