- 58 -
(4) Transmission cable specifi cations
(5) Connecting electrical connections
*1 Connected with simple remote controller. CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CVV, MVV
: PVC insulated PVC sheathed control cable
CPEVS
: PE insulated PVC jacketed shielded communication cable
(4)-1 Transmission cables
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
MA Remote controller cables
Sheathed 2-core cable (shielded)
CVVS
0.3
∼
1.25 mm
2
(0.75
∼
1.25 mm
2
)*1
Max.length: 200 m
External input
Sheathed multi-core cable (shielded)
CVVS or MVVS
0.3
∼
0.5 mm
2
Max.length: 100 m
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3
∼
1.25 mm
2
Rated voltage: L1-N: 220
∼
240 V
Rated load: 0.6 A
PWFY-P100VM-E-BU
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
MA Remote controller cables
Sheathed 2-core cable
CVV (unshielded)
0.3
∼
1.25 mm
2
(0.75
∼
1.25 mm
2
)*1
Max.length: 200 m
External input
Sheathed multi-core cable
CVV or MVV (unshielded)
0.3
∼
0.5 mm
2
Max.length: 100 m
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3
∼
1.25 mm
2
Rated voltage: L1-N: 220
∼
240 V
Rated load: 0.6 A
PWFY-P100, 200VM-E-AU
Note:
Ensure that the wiring is not pinched when fi tting the terminal box cover. Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
•
Fix power source external input/output line wiring to control box by using buffer bushing for tensile force to prevent
electric shock. (PG connection or the like.) Connect transmission wiring to transmission terminal block through the
knockout hole of control box using ordinary bushing.
•
After wiring is complete, make sure again that there is no slack on the connections, and attach the cover onto the
control box in the reverse order removal.
[Fig. IV. 1.(5).2]
(A) Screws
(B) Front panel
(C) Control box
(A) To prevent external tensile force from applying to the wiring
connection section of power source terminal block use buffer
bushing like PG connection or the like.
(B) External signal input cable
(C) External signal output cable
(D) Power source wiring
(E) Tensile force
(F) Use ordinary bushing
(G) Transmission cable and MA remote controller cable
(A)
(C)
(B)
(C)
(A)
(A)
(A)
(B)
(D)
(E)
(G)
(F)
Verify that the model name on the operating instructions on the cover of the control box is the same as the model name
on the nameplate.
Step 1
Remove the screws holding the terminal box cover in place.
[Fig. V.1.(5).1]
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnection, heating or fi re result.