59
English
7 Technical Data
7.1 Specifications
(1) Input specifications
Item
PV-S4200-IT
PV-S4600-IT
PV-S6000-IT
DC input voltage range
0 - 700 VDC
DC input current range
0 - 9ADC × 2
Number of input strings
2
(2) Output specifications
Item
PV-S4200-IT
PV-S4600-IT
PV-S6000-IT
Rated output
4.2 kW
4.6 kW
6.0 kW
Maximum output
4.2 kVA
5.1 kVA
6.0 kVA
Rated output voltage
230 VAC
Maximum output current
18.3 AAC
22.2 AAC
26.1 AAC
Grid-connected operation range
184 -276 VAC 49.7 - 50.3 Hz
Grid connectable
Single-phase, pair, 230 VAC
(Connectable to single-phase pair grid)
(3) PV inverter specifications
Item
PV-S4200-IT
PV-S4600-IT
PV-S6000-IT
Ambient requirements
Indoor/Outdoor (-25 - +50°C)
Maximum power conversion
efficiency
97.5 %
97.5 %
97.8 %
EUROPEAN efficiency
96.8 %
96.9 %
97.2 %
MPPT range
250-550 VDC
300-550 VDC
380*-550 VDC
Output fundamental wave power
factor
95 % (0.4kW or more)
Harmonic current distortion factor
Total 5 %, 3 % each (at rated output)
Night-time power consumption
0.5 W
Noise level
At front 1m, 45dB (A characteristics)
Conversion method
Voltage-type current control method
Switching method
Sine wave PWM method
Grounding method
Isolated (transformerless)
Power control
Operates within range of maximum output power,
maximum output current, and maximum input current.
However, once the internal temperature has reached
76°C, the output power is limited to prevent any further
rise.
Automatic start and stop
Activated by stop and start sequence
Cooling fan control
Controls the cooling fan based on internal temperature
and output power, to vary the airflow volume.
* When grid voltage is 230VAC