When an error occurs
LCD screen and LED lamps
Description
ERROR E-00
ITA:ENEL GUIDE
TOTAL 11358kWh
OUTPUT 0W
MAXIMUM 4508W
Abnormalities in the AC grid or PV system cause the safety
devices to activate, stopping grid-connected operation.
[E-00] (00 is a numeral) at the top right of the LCD screen
shows the error code.
For a description of the error codes, see p.61 “Error Codes”.
5.2.2 If the Error Lamp is Lit
When the Error lamp lit, take the following action.
Procedure
1. Turn OFF (
c
) the DC disconnectors at the bottom of the
PV inverter (DC1 and DC2).
2. Check that the LCD screen and all LED lamps are
extinguished, and then reset the DC disconnector to ON
( | ). (The PV inverter will restart operation.)
If the situation is not improved by the above action (the Error
lamp lit up again), take the following action.
1. Turn OFF (
c
) the DC disconnectors at the bottom of the
PV inverter (DC1 and DC2).
2. Turn OFF the AC disconnector or GFCI.
3. Contact the sales office for repairs.