64
OCH748
Request code
Request content
Description
(Display range)
Unit
Remarks
103 Error history 1 (latest)
Displays error history. (" --" is displayed if no history is present.)
Code
104 Error history 2 (second to last)
Displays error history. (" --" is displayed if no history is present.)
Code
105 Error history 3 (third to last)
Displays error history. (" --" is displayed if no history is present.)
Code
106 Abnormal thermistor display
(TH3/TH6/TH7/TH8/TH32)
3: TH3/TH32
6: TH6
7: TH7
8: TH8
0: No thermistor error
Sensor
number
107 Operation mode when the last error occurred
Displayed in the same way as request code "0".
―
108 Compressor-Operating current when the last error
occurred
0 to 50
A
109 Compressor-Accumulated operating time when the last
error occurred
0 to 9999
10 hours
110 Compressor-Number of operation times when the last
error occurred
0 to 9999
100 times
111 Discharge temperature when the last error occurred
−20 to 217
°C
112 Outdoor unit -Liquid pipe 1 temperature (TH3) when the
last error occurred
−40 to 90
°C
113 Water inlet temperature (TH32) when the last error
occurred
−40 to 101
°C
114 Plate HEX liquid pipe temperature (TH6) when the last
error occurred
−39 to 88
°C
115 Outdoor unit-Suction pipe temperature (TH33)
−39 to 88
°C
116 Outdoor unit-Ambient temperature (TH7) when the last
error occurred
−39 to 88
°C
117 Outdoor unit-Heatsink temperature (TH8) when the last
error occurred
−40 to 200
°C
118 Discharge superheat (SHd) when the last error occurred
0 to 255
°C
119 Sub-cool (SC) when the last error occurred
0 to 130
°C
120 Compressor-Operating frequency when the last error
occurred
0 to 255
Hz
121 Outdoor unit when the last error occurred
• Fan output step
0 to 16
Step
122 Outdoor unit when the last error occurred
• Fan 1 speed (Only for air conditioners with DC fan)
0 to 9999
rpm
123 Outdoor unit when the last error occurred
• Fan 2 speed (Only for air conditioners with DC fan)
0 to 9999
rpm
"0" is displayed if the air conditioner is
a single-fan type.
124
125 LEV (A) opening pulse when the last error occurred
0 to 500
Pulses
126 LEV (B) opening pulse when the last error occurred
0 to 500
Pulses
127 LEV (C) opening pulse when the last error occurred
0 to 500
Pulses
128
129 Condensing temperature (T63HS) when the last error
occurred
−39 to 88
°C
130 Thermostat ON time until operation stops due to error
0 to 999
Minutes