4-1. NOISE CRITERION CURVES
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
90
80
70
60
50
40
30
20
10
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
63
125
250
500
1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
BAND CENTER FREQUENCIES, Hz
PUZ-HWM140VHA(-BS)
PUZ-HWM140YHA(-BS)
COOLING
MODE
HEATING
53
SPL(dB)
53
LINE
1.5 m
1 m
MICROPHONE
UNIT
GROUND
4-2. STANDARD OPERATION DATA
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
11,900
14,000
Input
kW
3.97
3.14
Electrical
circuit
Outdoor unit
PUZ-HWM140VHA/ PUZ-HWM140YHA
Phase, Hz
1 / 3, 50
Voltage
V
230 / 400
Current
A
16.8 / 5.5
13.8 / 4.5
Refrigerant
circuit
Discharge pressure
MPa
2.83
2.2
Suction pressure
MPa
0.86
0.69
Discharge temperature
ºC
84
71
Condensing temperature ºC
47
37
Suction temperature
ºC
8
1
Water
conditions
Flow volume
L/min
34.1
40.1
Outlet water temperature
ºC
7
35
Outdoor
conditions
Intake air
temperature
D.B. ºC
35
7
W.B. ºC
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm
2
)