100
OCH634C
Notes
· High voltage is applied to the connector (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit
board and fan motor.)
Self check
Symptom : The outdoor fan cannot rotate.
1
2
Check method of DC fan motor (fan motor/outdoor multi controller circuit board)
Power supply check (Remove the connector (CNF1, 2))
Measure the voltage in the outdoor multi controller circuit
board.
TEST POINT
1
: V
DC
(between 1 (+) and 4 (
−
) of the fan connector): V
DC
310–340 V DC
TEST POINT
2
: V
CC
(between 5 (+) and 4 (
−
) of the fan connector): V
CC
15 V DC
No
Fail
Fail
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Fuse check
Check the fuse (F500) on outdoor
multi controller circuit board.
Correct the wiring.
Replace the outdoor multi controller circuit board.
Replace the outdoor multi controller
circuit board (MULTI.B.) (C.B) and
the defective fan motor.
Replace the outdoor
multi controller
circuit board.
Replace the defective fan motor.
Replace the defective fan motor.
Is the voltage normal?
Is there contact failure?
Yes
Yes
No
Did the fuse blow?
No
Yes
Check the operation of fan.
Yes
OK
Check the operation.
Complete.
Complete.
OK
Disconnect the FAN motor connector and
measure the resistance of connector pins.
Refer to “8-7. HOW TO CHECK THE PARTS”.