8
OCH634C
2-4. SYSTEM SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Outdoor unit <When using model 200 >
PU M Y - P 200 Y
K M 1 - BS
Refrigerant
R410A
Indicates equivalent
to Cooling capacity
Power supply
Y
: 3-phase
380/400/415 V, 50/60 Hz
Outdoor unit
model type
Sub-number
M-NET
control
Frequency
conversion
controller
Outdoor unit
MULTI-S
(kcal/h)
Salt proof
type
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : D.B. 27°C/ W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C/ W.B. 6°C
(3) Operating temperature range
Notes: D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*10 to 52°C D.B. : When connecting PKFY-P15/P20/P25VBM, PFFY-P20/25/32VKM, PFFY-P20/25/32VLE(R)M, PEFY-P40/63VMA3-E; and
M series, S series, and P series type indoor unit.
Service Ref.
PUMY-P200YKM1
PUMY-P200YKM1-BS
Capacity
Cooling (kW)
22.4
Heating (kW)
25.0
Compressor (kW)
5.4
Cooling
Heating
Indoor-side intake air temperature
W.B. 15 to 24°C
D.B. 15 to 27°C
Outdoor-side intake air temperature
D.B. −5 to 52°C*
W.B. −20 to 15°C
■ When connecting fresh air type indoor unit
Capacity of Fresh
air type indoor
Cooling
Heating
Indoor-side and Outdoor-side
intake air temperature
P200
D.B. 21 to 43°C*
W.B. 15.5 to 35°C
D.B. −10 to 20°C**
*Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is lower than 21°C D.B.
**Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is higher than 20°C D.B.