Check code
1302
(UE)
High pressure trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 4 of 4
Yes
Yes
Yes
No
No
No
Continued from the previous page.
Is the voltage normal value?
Is it free from any trace of over-
heating or burning?
Is the resistance detected?
Is the resistance detected?
Check the voltage (*) and appearance of
the outdoor controller board.
Disconnect the thermistor wiring to check
the resistance.
Disconnect the indoor LEV wiring and
check the resistance.
Replace the outdoor controller board.
Replace the thermistor.
Replace the indoor LEV.
Replace the indoor controller board.
*For the voltage, refer to "8-8.HOW
TO CHECK THE COMPONENTS".
54
55
OCH740