When installing the outdoor unit on a rooftop or other location unprotected from the 
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. 
Strong wind entering the air outlet may impede the normal air

ß

 ow and a malfunction 

may result.
The following shows three examples of precautions against strong winds.

1

  Face the air outlet towards the nearest available wall about 50 cm away from the 

wall. (Fig. 2-3)

2

  Install an optional air guide if the unit is installed in a location where strong winds 

from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)

 

A

   Air outlet guide

3

  Position the unit so that the air outlet blows perpendicularly to the seasonal wind 

direction, if possible. (Fig. 2-5)

 

B

   Wind direction

x

›

©

£

x

›

©

Ÿ

x

›

©

º

«

¬

­

¬

«

¬

¯

»

¼

±

°

±

¹

¸

·

´

´

°

±

½

·

¹

°

±

½

´

¼

µ

¾

¸

²

µ

µ

¿

¾

±

°

¸

À

&

¼

Á

¼

¿

¸

µ

¸

»

¼

´

·

¹

¸

Â

·

½

¼

Ã

Minimum  dimensions  are  as  follows,  except  for  Max.,  meaning  Maximum  dimen-
sions, indicated.
The 

Þ

 gures in parentheses are for SW100, 120 models.

Refer to the 

Þ

 gures for each case.

1

 Obstacles at rear only (Fig. 2-6)

2

 Obstacles at rear and above only (Fig. 2-7)

 

•   Do not install the optional air outlet guides for upward air

ß

 ow.

3

 Obstacles at rear and sides only (Fig. 2-8)

 

*  350 for SW50.

4

 Obstacles at front only (Fig. 2-9)

 

*   When using an optional air outlet guide, the clearance for SW100, 120 models is 500 mm or 

more.

5

 Obstacles at front and rear only (Fig. 2-10)

 

*   When using an optional air outlet guide, the clearance for SW100, 120 models is 500 mm or 

more.

6

 Obstacles at rear, sides, and above only (Fig. 2-11)

 

*  350 for SW50.

 

•   Do not install the optional air outlet guides for upward air

ß

 ow.

«

¬

­

¬

Ä

¬

¯

»

¼

±

°

±

¹

¸

·

´

´

°

±

½

Å

¾

´

¸

°

Â

´

¼

µ

¾

¸

²

µ

µ

¿

¾

±

°

¸

¹

À

&

¼

Á

¼

¿

¸

µ

¸

»

¼

´

·

¹

¸

Â

·

½

¼

Ã

Leave  350  mm  for  SW50  and  10  mm  for  SW75-120  space  or  more  between  the 
units.
The 

Þ

 gures in parentheses are for SW100, 120 models.

Refer to the 

Þ

 gures for each case.

1

 Obstacles at rear only (Fig. 2-12)

2

 Obstacles at rear and above only (Fig. 2-13)

 

•   No more than 3 units must be installed side by side. In addition, leave space as shown.

 

•   Do not install the optional air outlet guides for upward air

ß

 ow.

3

 Obstacles at front only (Fig. 2-14)

 

*   When using an optional air outlet guide, the clearance for SW100, 120 models is 1000 mm 

or more.

4

 Obstacles at front and rear only (Fig. 2-15)

 

*   When using an optional air outlet guide, the clearance for SW100, 120 models is 1000 mm 

or more.

5

 Single parallel unit arrangement (Fig. 2-16)

 

*   When using an optional air outlet guide installed for upward air

ß

 ow, the clearance is 500 

(1000) mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-17)

 

*   When using an optional air outlet guide installed for upward air

ß

 ow, the clearance is 1000 

(1500) mm or more.

7

 Stacked unit arrangement (Fig. 2-18)

 

•   The units can be stacked up to two units high.

 

•   No more than 2 stacked units must be installed side by side. In addition, leave space as 

shown.

›

x

›

x

Æ

 

 

 

•   Avoid locations exposed to direct sunlight or other sources of heat.
•   Select  a  location  from  which  noise  emitted  by  the  unit  will  not  inconvenience 

neighbors.

•   Select a location permitting easy wiring and pipe access to the power source and 

indoor unit.

•   Avoid locations where combustible gases may leak, be produced, 

ß

 ow, or accu-

mulate.

•   Note that water may drain from the unit during operation.
•   Select a level location that can bear the weight and vibration of the unit.
•   Avoid locations where the unit can be covered by snow. In areas where heavy 

snow fall is anticipated, special precautions such as raising the installation loca-
tion or installing a hood on the air intake must be taken to prevent the snow from 
blocking the air intake or blowing directly against it. This can reduce the air

ß

 ow 

and a malfunction may result.

•   Avoid locations exposed to oil, steam, or sulfuric gas.
•   Use the transportation handles of the outdoor unit to transport the unit. If the unit 

is carried from the bottom, hands or 

Þ

 ngers may be pinched.

›

x

Ÿ

x

Ç

 

œ

Ç



œ

x

›

©

›



x

›

©

›

Ŷ

#

¯

È

É

Ê

®

Ë

Ë

Ê

®

«

Ë

Ŷ

#

¯

É

Ë

80

9

30

0+

23

6

3

0

50

0

62

36

0

(mm)

154

.5

Summary of Contents for PUHZ-SW HA Series

Page 1: ...anuel d installation de l appareil intérieur pour une utilisation sûre et correcte L anglais est l original Les versions fournies dans d autres langues sont des traductions de l original Lees voor een veilig en juist gebruik deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van het buitenapparaat begint Het Engels is het origineel De...

Page 2: ... A B M Q V X O H J Q H T I A C L B H I B D E H B A C N T N O H B N O A C N O A N Q c H D R H M I T B N O H Q L Q N H U _ D K K A J Q H U H O A C D A K I A D K J B H T B Q L Q N H U U A K I J C N D T C T B J C D N P B H A Z M T _ C V C N O H _ T B Q N A Q H N O D Q T J K M K H A M N T A Q H B D T J Q D U c H M D U H C N N T Q H J B D C E c B T M J N Q A I H N L V W q Q H T C K L A H Q Q T B D H Q A...

Page 3: ... D E H B A C N c D c H Q V b A Z H Q J B H N O H D C Q D M H Q T I N O H c D c H Q A B H K H A C A C M M T C T N T C N A D C A C L O A B U I J K T C N A U D C A C N Q Q J O A Q Q J K I J B D T U c T J C M Q T S D M A C N Q M H P B D Q T B M J Q N V q Q H c D c H Q _ D N O N O H Q c H D R H M N O D Z C H Q Q V s d H I H B N T e V f V t T N H N O H I T K K T _ D C E D I B H J Q D C E H S D Q N D C E...

Page 4: ...ear only Fig 2 12 2 Obstacles at rear and above only Fig 2 13 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airßow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for SW100 120 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an op...

Page 5: ... T L Q H A U K H Q Q c D c H Q N T T C C H N N O H B H I B D E H B A C N c D c H Q V q Q H B H I B D E H B A C N c D c H Q _ D N O N O H N O D Z C H Q Q H Q Q c H D R H M D C N O H N A P K H N T N O H P H K T _ V b A Z H Q J B H N O H D C Q D M H Q T I N O H c D c H Q A B H K H A C A C M M T C T N T C N A D C A C L O A B U I J K T C N A U D C A C N Q Q J O A Q Q J K I J B D T U c T J C M Q T S D M...

Page 6: ... valve D Service panel E Bend radius 100 mm 150 mm x x z x For SW50 Remove the service panel D 1 screw For SW75 120 Remove the service panel D 3 screws and the front piping cover A 2 screws and rear piping cover B 2 screws SW75 4 screws SW100 120 1 Perform refrigerant piping connections for the indoor outdoor unit when the out door unit s stop valve is completely closed 2 Vacuum purge air from the...

Page 7: ...pes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap for SW75 120 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result x x z z Additional charging is not necessary if the pipe length does not exceed 10 m If the pi...

Page 8: ... å æ ç Ŷ ä å æ ç è é ê ë ì í î ê ï ë ð ñ é ê ë ò ê ó ô ë õ ï ë ë ê î é ñ ê ï ë ë ö ë ò ê ñ ó ò ö ø é ù ó õ ñ ë ú é ô ë û û ü ñ ó ý þ õ ë ñ ô ó ò ó ý þ ÿ ø ë õ ü ñ ë ê é ñ ë ó ý õ ê ö ö ó ê Ŷ ä å æ ç ü ê ó é ý ì ë õ ü ñ ë ê é ó ý õ ê ö ö è ó ý ë ó ê ï é ü ê è ó ý ë ÿ ó ê ò é ü ö û ò ü õ ë û ú þ ë ê é ü ý ó ê 1 Remove the service panel 2 Wire the cables referring to the Fig 7 1 and the Fig 7 2 A Ind...

Page 9: ...aker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m 3 The 10 m wire is attached in the remote controller accessory 4 The Þgures are NOT always against the ground S3 terminal has 24 VDC against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device å 0 1 2 3 ...

Page 10: ... lit Only set the SWP switch push button type to ON if the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than 3 minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until compressor has been stopped for 3 minutes and then set the SWP switch to ON again A p 3 Because the unit automatically stops in about 2 to 3 ...

Page 11: ...9 X 10 Y 11 Z 12 1 2 3 Year of manufacture western calendar 2014 ĺ 4 2015 ĺ 5 U outdoor unit SW50 Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 ĺ 4 2015 ĺ 5 SW75 100 120 ...

Page 12: ...úa õdaki hususlarõ yalnõzca kendi sorumlulu unda beyan eder ɧɚɫɬɨɹɳɢɦ ɡɚɹɜɥɹɟɬ ɢ ɛɟɪɟɬ ɧɚ ɫɟɛɹ ɢɫɤɥɸɱɢɬɟɥɶɧɭɸ ɨɬɜɟɬɫɬɜɟɧɧɨɫɬɶ ɡɚ ɬɨ ɱɬɨ ɤɨɧɞɢɰɢɨɧɟɪɵ ɢ ɬɟɩɥɨɜɵɟ ɧɚɫɨɫɵ ɨɩɢɫɚɧɧɵɟ ɧɢɠɟ ɢ ɩɪɟɞɧɚɡɧɚɱɟɧɧɵɟ ɞɥɹ ɷɤɫɩɥɭɚɬɚɰɢɢ ɜ ɠɢɥɵɯ ɩɨɦɟɳɟɧɢɹɯ ɬɨɪɝɨɜɵɯ ɡɚɥɚɯ ɢ ɧɚ ɩɪɟɞɩɪɢɹɬɢɹɯ ɥɟɝɤɨɣ ɩɪɨɦɵɲɥɟɧɧɨɫɬɢ erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersiell...

Page 13: ... yalnõzca kendi sorumlulu unda beyan eder ɧɚɫɬɨɹɳɢɦ ɡɚɹɜɥɹɟɬ ɢ ɛɟɪɟɬ ɧɚ ɫɟɛɹ ɢɫɤɥɸɱɢɬɟɥɶɧɭɸ ɨɬɜɟɬɫɬɜɟɧɧɨɫɬɶ ɡɚ ɬɨ ɱɬɨ ɤɨɧɞɢɰɢɨɧɟɪɵ ɢ ɬɟɩɥɨɜɵɟ ɧɚɫɨɫɵ ɨɩɢɫɚɧɧɵɟ ɧɢɠɟ ɢ ɩɪɟɞɧɚɡɧɚɱɟɧɧɵɟ ɞɥɹ ɷɤɫɩɥɭɚɬɚɰɢɢ ɜ ɠɢɥɵɯ ɩɨɦɟɳɟɧɢɹɯ ɬɨɪɝɨɜɵɯ ɡɚɥɚɯ ɢ ɧɚ ɩɪɟɞɩɪɢɹɬɢɹɯ ɥɟɝɤɨɣ ɩɪɨɦɵɲɥɟɧɧɨɫɬɢ erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrie...

Page 14: ...izce dir Di er dillerdeki sürümler aslõnõn çevirisidir á ø ì ì Û Ý So utucu kaça õ bo ulmaya neden olabilir EN378 1 uyarõnca uygun havalandõrma sa layõn Borular etrafõna yalõtõm yapõldõ õndan emin olun Borulara do rudan çõplak elle dokunulmasõ yanõklara veya so uk õsõrõklarõna neden olabilir Kazara yutmamak için pilleri kesinlikle hiçbir amaçla a zõnõzda tutmayõn Pillerin yutulmasõ bo ulmaya ve ve...

Page 15: ...wolno wkáadaü baterii do ust z jakiegokolwiek powodu aby uniknąü przypadkowego poákniĊcia PoákniĊcie baterii moĪe spowodowaü zadáawienie i lub zatrucie Zainstalowaü urządzenie na sztywnej konstrukcji aby zapobiec nadmiernemu haáasowi i wibracjom Poziom dĨwiĊku A nie przekracza 70 dB W sklepach w przemyĞle lekkim i w gospodarstwach rolnych urządzenie powinni obsáugiwaü profesjonalni lub przeszkolen...

Page 16: ...0 200 200 300 100 200 500 1000 100 150 500 1000 200 300 1000 1500 0 1 1 1 2 0 3 1 1 4 5 6 6 7 8 6 6 9 500 1000 400 600 1000 2000 100 150 1000 1500 400 600 2000 3000 300 500 1000 1500 500 800 150 A B C D E D D D D F D G D H D D A D B ...

Page 17: ......

Page 18: ... MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travellers Lane HatÞeld Herts AL10 8XB England U K Polish Branch Krakowska 50 PL 32 083...

Reviews: