2-1. SPECIFICATION
2.-1-1. PUHZ-HRP200YKA
<Reference data> Plate heat exchanger (ACH50-50 plates) *2pcs [connected in parallel]
Nominal water
fl
ow
L/min
65.9
Heating
(A7/W35)
Capacity
kW
23.0
COP
3.65
Power input
kW
6.31
Heating
(A7/W45)
Capacity
kW
23.0
COP
2.77
Power input
kW
8.29
Heating
(A7/W55)
Capacity
kW
23.0
COP
2.27
Power input
kW
10.15
Heating
(A-7/W35)
Capacity
kW
23.0
COP
2.24
Power input
kW
10.25
Heating
(A-7/W45)
Capacity
kW
23.0
COP
1.93
Power input
kW
11.90
Heating
(A-7/W55)
Capacity
kW
23.0
COP
1.66
Power input
kW
13.86
Heating
(A-15/W35)
Capacity
kW
23.0
COP
2.05
Power input
kW
11.24
Heating
(A-15/W45)
Capacity
kW
22.2
COP
1.80
Power input
kW
12.36
Heating
(A-15/W55)
Capacity
kW
21.2
COP
1.36
Power input
kW
15.64
Heating
(A2/W35)
Capacity
kW
23.0
COP
2.37
Power input
kW
9.69
Nominal water
fl
ow
L/min
57.3
Cooling
(A35/W7)
Capacity
kW
20.00
EER
2.22
Power input
kW
9.01
Cooling
(A35/W18)
Capacity
kW
20.00
EER
3.55
Power input
kW
5.64
Rating conditions
Nominal operating condition
Heating (A2/W35)
Outside air temperature (Dry-bulb)
+ 2 °C
Outside air temperature (Wet-bulb)
+ 1 °C
Water temperature (inlet/outlet)
+ 30 °C/+ 35 °C
Heating (A7/W35)
Outside air temperature (Dry-bulb)
+ 7 °C
Outside air temperature (Wet-bulb)
+ 6 °C
Water temperature (inlet/outlet)
+ 30 °C/+ 35 °C
Heating (A7/W45)
Outside air temperature (Dry-bulb)
+ 7 °C
Outside air temperature (Wet-bulb)
+ 6 °C
Water temperature (inlet/outlet)
+ 40 °C/+ 45 °C
Heating (A7/W55)
Outside air temperature (Dry-bulb)
+ 7 °C
Outside air temperature (Wet-bulb)
+ 6 °C
Water temperature (inlet/outlet)
+ 50 °C/+ 55 °C
Heating (A-7/W35)
Outside air temperature (Dry-bulb)
- 7 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 35 °C
Heating (A-7/W45)
Outside air temperature (Dry-bulb)
- 7 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 45 °C
Heating (A-7/W55)
Outside air temperature (Dry-bulb)
- 7 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 55 °C
Heating (A-15/W35)
Outside air temperature (Dry-bulb)
- 15 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 35 °C
Heating (A-15/W45)
Outside air temperature (Dry-bulb)
- 15 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 45 °C
Heating (A-15/W55)
Outside air temperature (Dry-bulb)
- 15 °C
Outside air temperature (Wet-bulb)
—
Water temperature (inlet/outlet)
— °C/+ 55 °C
Cooling (A35/W7)
Outside air temperature (Dry-bulb)
+ 35 °C
Outside air temperature (Wet-bulb)
+ 24 °C
Water temperature (inlet/outlet)
+ 12 °C/+ 7 °C
Cooling (A35/W18)
Outside air temperature (Dry-bulb)
+ 35 °C
Outside air temperature (Wet-bulb)
+ 24 °C
Water temperature (inlet/outlet)
+ 23 °C/+ 18 °C
Note: "COP" and "Power input" in the above table are values that does
NOT
contains the "pump input (based on EN 14511)".