INDOOR-OUTDOOR CONNECTING CABLE (HRP200)
Cross section of cable
Wire size (mm
2
)
Number of wires
Polarity
L (m)*6
Round
2.5
3
Clockwise : S1-S2-S3
*Pay attention to stripe of yellow and green
(30)
*2
Flat
2.5
3
Not applicable
(Because center wire has no cover
fi
nish)
Not applicable
*5
Flat
1.5
4
From left to right : S1-Open-S2-S3
(18)
*3
Round
2.5
4
Clockwise : S1-S2-S3-Open
*Connect S1 nad S3 to the opposite angle
(30)
*4
*1 :Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*2 :In case that cable with stripe of yellow and green is available.
*3 :In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm
2.
*4 :In case of regular polarity connection (S1-S2-S3).
*5 :In the
fl
at cables are connected as this picture, they can be used up to 30 m.
*6 :Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or
materials, etc.
(3C Flat cable × 2)
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication error if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at
the intermediate connection point.