background image

11

1 2 3 4 5 6

9.1. Low noise mode (on-site modifi cation) (Fig. 9-1)

By performing the following modifi cation, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
•  

The ability varies according to the outdoor temperature and conditions, etc.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

2

  SW1 ON: Low noise mode

 

SW1 OFF: Normal operation

A

  Circuit diagram example (low noise mode)

B

 On-site arrangement

C

  External input adapter (PAC-SC36NA)

D

  Outdoor unit control board

E

  Max. 10 m

9.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.

1

  Supply power (circuit breaker).

 *  

When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 
displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

2

  After the gas stop valve is closed, set the SWP switch on the control board of the 

outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and 
outdoor units) start operating and refrigerant collecting operation begins. LED1 
and LED2 on the control board of the outdoor unit are lit.

 *  

Only set the SWP switch (push-button type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than 
three minutes after the compressor stops, the refrigerant collecting operation 
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.

*  Set the refrigerant address using the DIP switch of the outdoor unit.

1

  Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor 
unit (non-polar).

2

 When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.

Note:
In single refrigerant system (twin/triple), there is no need of wiring 

2

.

A

 Outdoor unit

B

 Indoor unit

C

  Master remote controller

D

  Subordinate remote controller

E

  Standard 1:1 (Refrigerant address = 00)

F

  Simultaneous twin (Refrigerant address = 01)

G

  Simultaneous triple (Refrigerant address = 02)

E

  SW 1 - 3 ~ 6

F

  SW 1 - 3 ~ 6

G

  SW 1 - 3 ~ 6

 Red

A

B

C

D

E

SW1

CNDM

3

1

Fig. 9-1

3

  Because the unit automatically stops in about two to three minutes after the 

refrigerant collecting operation (LED1 and LED2 are lit), be sure to quickly close 
the gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, 
open the liquid stop valve completely, and then repeat step 

2

 after three min-

utes have passed.

 *  

If the refrigerant collecting operation has been completed normally (LED1 and 
LED2 are lit), the unit will remain stopped until the power supply is turned off.

4

  Turn off the power supply (circuit breaker).

10. System control (Fig. 10-1)

Fig. 9-1

SW1
Function table

 <SW1>

Function

Operation according to switch setting

ON

OFF

SW1
function 
settings

1 Compulsory 

defrosting

Start

Normal

2 Error history 

clear

Clear

Normal

3
4
5
6

Refrigerant 
system ad-
dress setting

Settings for outdoor unit addresses 
0 to 15

TB1

A

G

F

A

A

E

B

B

B

B

B

B

D

C

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

1

1

2

 ON
 OFF

 ON
 OFF

 ON
 OFF

3    4    5    6

3    4    5    6

3    4    5    6

 Brown

 Orange

 ON
 OFF

2

A

   Circuit diagram example (Demand function)

B

   On-site arrangement

C

  External input adapter (PAC-SC36NA)

D

  Outdoor unit control board

E

  Max. 10 m

9.2. Demand function (on-site modifi cation) (Fig. 9-2)

By performing the following modifi cation, energy consumption can be reduced to 0
–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

2

  By setting SW7-1 and SW7-2 on the control board of the outdoor unit, the ener-

gy consumption (compared to the normal consumption) can be limited as shown 
below.

SW7-1

SW7-2

Energy consumption (SW2 ON)

OFF

OFF

0% (Stop)

ON

OFF

50%

OFF

ON

75%

 Red

A

B

C

D

E

SW2

CNDM

3

1

 Brown

 Orange

Fig. 9-2

8. Initial settings for refrigerant leakage detection function

9. Special Functions

[Display  ] Waiting for stabilization

Stabilized

After 45 minutes

D

Fig. 8-3

Press

FILTER

 ( ) button to confirm. (Fig. 8-3)

How to finish the initial learning

Once the unit’s operation is stabilized, the initial learning is completed.

Press

TEST

 button for more than three seconds to cancel the initial learning.

The initial learning can also be cancelled by pressing 

ON/OFF

 button.

* Refer to the Technical Manual for the refrigerant leakage detection judgment method.

Summary of Contents for PUHZ-HA2

Page 1: ...n de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓ...

Page 2: ... air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories a...

Page 3: ...eration The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Do not use refrigerant other than R410A r...

Page 4: ...de by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 5 Single paralle...

Page 5: ...hoons or strong winds An incorrectly installed unit may fall down and cause damage or injuries mm M10 3 8 bolt Base As long as possible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refr...

Page 6: ...88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 Installing the refrigerant piping Fig 4 3 AFront piping cover BPiping cover CStop valve DService panel EBend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 3 Remove the service panel D three screws and the front piping cover A two screws and rear piping cover B two screws 1 Perform refrigerant piping connections for the indoor outdoor unit when the ...

Page 7: ...ockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length ...

Page 8: ...s to confirm if the pipes can be used If the diameter of the existing gas side pipe is bigger than the specified diameter turn SW8 1 on Measure the existing pipe thickness and check for damage The existing pipe thickness meets specifica tions and the pipes are not damaged Check if the existing air conditioner can operate After operating the cooling system for about 30 minutes do a pump down work D...

Page 9: ...rminals are NOT electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and Indoor Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when ...

Page 10: ...l on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches easily 7 3 Test run 7 3 1 Using SW4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is...

Page 11: ...win Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 9 1 3 Because the unit automatically stops in about two to three minutes after the refrigerant collecting operation LED1 and LED2 are lit be sure to quickly close the gas stop valve When LED1 and LED2 are lit and the outdoor unit is stopped open the liquid stop va...

Page 12: ......

Page 13: ...ig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 Fig 2 10 Fig 2 9 Fig 2 8 Fig 2 6 150 300 1000 Max 500 200 300 200 1000 150 1000 250 250 1500 500 Max 500 300 1500 500 1500 Max 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 ...

Page 14: ...RMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K RG79D355H03 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Reviews: