background image

6

4. Installing the refrigerant piping

4.3. Refrigerant piping (Fig. 4-4)

Remove the service panel 

D

 (3 screws) and the front piping cover 

A

 (2 screws) 

and rear piping cover 

B

 (2 screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the out-

door unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  A high-performance vacuum pump is used at the stop valve service port to main-

tain a vacuum for an adequate time (at least 1 hour after reaching –101 kPa (5 
Torr)) in order to vacuum dry the inside of the pipes. Always check the degree 
of vacuum at the gauge manifold. If there is any moisture left in the pipe, the de-
gree of vacuum is sometimes not reached with short-time vacuum application. 

 

 After vacuum drying, completely open the stop valves (both liquid and gas) for 
the outdoor unit. This completely links the indoor and outdoor refrigerant circuits.

 •  

If the vacuum drying is inadequate, air and water vapor remain in the refriger-
ant circuits and can cause abnormal rise of high pressure, abnormal drop of 
low pressure, deterioration of the refrigerating machine oil due to moisture, 
etc.

 •  

If the stop valves are left closed and the unit is operated, the compressor and 
control valves will be damaged.

 •  

Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.

 •  

Do not use the refrigerant from the unit to purge air from the refrigerant lines.

 •  

After the valve work is completed, tighten the valve caps to the correct torque: 
20 to 25 N·m (200 to 250 kgf·cm).

 

 

 Failure to replace and tighten the caps may result in refrigerant leakage. In 
addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

  Use sealant to seal the ends of the pipe cover around the pipe connection sec-

tions to prevent water from entering the thermal insulation.

4.4. Refrigerant pipe airtight testing method(Fig.4-5)

(1) Connect the testing tools.
 •  

Make sure the stop valves 

A B

 are closed and do not open them.

 •  

Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

.

(2)  Do not add pressure to the specifi ed pressure all at once; add pressure little by little.
 

1

  Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait 5 minutes, and make sure the pres-

sure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait 5 minutes, and make sure the 

pressure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the specifi ed pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

 •  

If the surrounding temperature changes by 1 °C, the pressure will change by 
about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.
(1) Gas side(Fig. 4-6)

1

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-

clockwise direction to open.

2

  Make sure that the stop valve is open comletely,push in the handle and rotate 

the cap back to its original position.

(2) Liquid side(Fig. 4-7)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go 

with the use of a 4 mm hexagonal wrench. Stop turning when it hits the stop-
per.

 

(ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely and rotate the cap back to 

its original position.

Refrigerant pipes are protectively wrapped

•   The pipes can be protectively wrapped up to a diameter of ø90 before or after 

connecting the pipes. Cut out the knockout in the pipe cover following the 
groove and wrap the pipes. 

Pipe inlet gap

•   Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-

main. (If the gaps are not closed, noise may be emitted or water and dust will 
enter the unit and breakdown may result.)

 •  

Be careful when installing multiple units. Connecting to an incorrect indoor unit 
can lead to abnormally high pressure and have a serious effect on operation 
performance.

4.6. Addition of refrigerant

•  

Additional charging is not necessary if the pipe length does not exceed 20 m for 
BP100-BP140 and 30 m for BP170-BP250.

•  

If the pipe length is exceeded, charge the unit with additional R410A refrigerant 
according to the permitted pipe lengths in the following table.
 *  

When the unit is stopped, charge the unit with the additional refrigerant 
through the liquid stop valve after the pipe extensions and indoor unit have 
been vacuumized.

 

 

 When the unit is operating, add refrigerant to the gas check valve using a 
safety charger. Do not add liquid refrigerant directly to the check valve.

*  

After charging the unit with refrigerant, note the added refrigerant amount 
on the service label (attached to the unit).

 

 Refer to the “1.5. Using R410A refrigerant air conditioners” for more infor-
mation.

Models

Permitted

    pipe

   length

Permitted

 vertical 

difference

Additional refrigerant charging amount

21-30m

31-40m

41-50m

51-60m

61-70m

BP100

~50m

~30m

0.6kg

1.2kg

1.8kg

BP125

BP140

BP170

~70m

~30m

0.9kg

1.8kg

2.7kg

3.6kg

BP200

BP250

1.2kg

2.4kg

3.6kg

4.8kg

A

 Front piping cover

B

 Piping cover

C

 Stop valve

D

 Service panel

E

 Bend radius : 100 mm-150 mm

Fig. 4-4

A

 Stop valve <Liquid side>

B

 Stop valve <Gas side>

C

 Service port

D

 Open/Close section

E

 Local pipe

F

 Seal section

(Seal the end of the heat insulation

material at the pipe connection section

with whatever seal material you have on

hand so that water does not infi ltrate the

heat insulation material.)

G

 Pipe cover

H

 Do not use a wrench here.

Refrigerant leakage may result.

I

 Double spanner section

(Do not apply a spanner other than to

this section. Doing so would cause 

refrigerant leaks.)

A

 Valve

B

 Unit side

C

 Operation section

D

 Cap

E

 Local pipe side

F

 Pipe cover

G

 Service port

H

 Wrench hole

I

 Double spanner section

(Do not apply a spanner other than to this section. Doing

so would cause refrigerant leaks.)

J

 Seal section

(Seal the end of the heat insulation material at the pipe connection

section with whatever seal material you have on hand

so that water does not infi ltrate the heat insulation material.)

K

 Handle

Fig. 4-5

Fig. 4-6

Fig. 4-7

(1)

(2)

Summary of Contents for PUHZ-BP HA

Page 1: ...R INSTALLER Air Conditioners PUHZ BP HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English ...

Page 2: ...the outdoor unit must be firmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock or fire may result When installing or moving the air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause press...

Page 3: ...xed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use a vacuum pump with a reverse flow check valve If the vacuum pump oil flows backward into the refrigerant lines refriger ant oil deterioration may result Use the following tools specifically designed for use w...

Page 4: ...uides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for BP125 BP250 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for BP125 BP250 models is 1000 mm or more When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm or mor...

Page 5: ...aks after connections are completed Apply refrigerating machine oil over the entire flare seat surface C Fig 4 1 Use the flare nuts for the following pipe size D Fig 4 1 When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the...

Page 6: ...door unit model Use the appropriate method to open the stop valves 1 Gas side Fig 4 6 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counter clockwise direction to open 2 Make sure that the stop valve is open comletely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 7 1 Remove the cap and turn the valve rod counterclockwise as far as it...

Page 7: ...eaker E Earth For Heater For Heater For Heater For Heater For Power BP170 BP250 only Fig 6 1 BP170 BP250 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it F Power supply terminal block L1 L2 L3 N G Indoor outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clampthe cables so that they do not contact the center of the service pane...

Page 8: ...it power supply 5 Min 4 Indoor unit Outdoor unit Cable length 50 m 3 4 Polar Cable length 80 m 3 6 Polar Indoor unit Outdoor unit earth 1 Min 2 5 Remote controller Indoor unit 2 0 3 Non polar Circuit rating Outdoor unit L1 N L2 N L3 N AC 220 230 240 V Indoor unit Outdoor unit S1 S2 AC 220 230 240 V Indoor unit Outdoor unit S2 S3 DC 24 V Remote controller Indoor unit DC 12 V 2 1 3 4 4 4 1 A breaker...

Page 9: ... 1 MΩ the compressor is faulty or the resis tance dropped due the accumulation of refrigerant in the compressor 3 After connecting the wires to the compressor the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accumulation of refrigerant in the com pressor Th...

Page 10: ...here is no need of wiring 2 A Outdoor unit B Indoor unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes after the refrigerant colle...

Page 11: ...11 Fig 2 11 Fig 2 13 Fig 2 14 Fig 2 16 Fig 2 17 Fig 2 10 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 12 Fig 2 15 Fig 2 18 Fig 2 9 ...

Page 12: ...00 8310 JAPAN BH79D068K03 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: