background image

600

600

175

175

950

25

330

370

B

4

2. Installation location 

2.4. Ventilation and service space

2.4.1. Windy location installation

When installing the outdoor unit on a rooftop or other location unprotected 
from the wind, situate the air outlet of the unit so that it is not directly exposed 
to strong winds. Strong wind entering the air outlet may impede the normal 
airfl ow and a malfunction may result.
The following shows 3 examples of precautions against strong winds.

1

  Face the air outlet towards the nearest available wall about 50 cm away 

from the wall. (Fig. 2-3) [for BP170-BP250 models : 100cm]

2

  Install an optional air guide if the unit is installed in a location where strong 

winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)

 

A

   Air outlet guide

3

  Position the unit so that the air outlet blows perpendicularly to the seasonal 

wind direction, if possible. (Fig. 2-5)

 

B

   Wind direction

D

Fig. 3-1

2.4.2. When installing a single outdoor unit (Refer to the last page)

Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.

The fi gures in parentheses are for BP125- BP250 models.

1

 Obstacles at rear only (Fig. 2-6)

2

 Obstacles at rear and above only (Fig. 2-7)

3

 Obstacles at rear and sides only (Fig. 2-8)

4

 Obstacles at front only (Fig. 2-9)

5

 Obstacles at front and rear only (Fig. 2-10)

 

•  

When using an optional air outlet guide, the clearance for BP125-BP250 models is 

500 mm or more.

6

 Obstacles at rear, sides, and above only (Fig. 2-11)

 

•  

Do not install the optional air outlet guides for upward airfl ow.

2.4.3. When installing multiple outdoor units (Refer to the last page)

Leave 10 mm space or more between the units.

1

 Obstacles at rear only (Fig. 2-12)

2

 Obstacles at rear and above only (Fig. 2-13)

 

•  

No more than 3 units must be installed side by side. In addition, leave space as 

shown.

 •  

Do not install the optional air outlet guides for upward airfl ow.

3

 Obstacles at front only (Fig. 2-14)

 

•   When using an optional air outlet guide, the clearance for BP125-BP250 models is 

1000 mm or more.

4

 Obstacles at front and rear only (Fig. 2-15)

 

•   When using an optional air outlet guide, the clearance for BP125-BP250 models is 

1000 mm or more.

 

•   When using an optional air outlet guide installed for upward airfl ow, the clearance is 

500 (1000) mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-17)

 

•   When using an optional air outlet guide installed for upward airfl ow, the clearance is 

1000 (1500) mm or more.

7

 Stacked unit arrangement (Fig. 2-18)

 

•  

The units can be stacked up to 2 units high.

 •  

No more than 2 stacked units must be installed side by side. In addition, leave 

space as shown.

3. Installing the outdoor unit

•  

Be sure to install the unit in a sturdy, level surface to prevent rattling noises dur-
ing operation. (Fig. 3-1)

<Foundation specifi cations>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

•  

Make sure that the length of the foundation bolt is within 30 mm of the bottom 
surface of the base.

•  

Secure the base of the unit fi rmly with 4-M10 foundation bolts in sturdy locations. 

Installing the outdoor unit

•  

Do not block the vent. If the vent is blocked, operation will be hindered and 
breakdown may result.

•  

In addition to the unit base, use the installation holes it fi xes top panel on the 
back of the unit to attach wires, etc., if necessary to install the unit. Use self-
tapping screws (ø5 × 15 mm or less) and install on site.

 Warning:

•  

The unit must be securely installed on a structure that can sustain its 
weight. If the unit is mounted on an unstable structure, it may fall down 
and cause damage or injuries.

•  

The unit must be installed according to the instructions in order to mini-
mize the risk of damage from earthquakes, typhoons, or strong winds. An 
incorrectly installed unit may fall down and cause damage or injuries.

A

 

M10 (3/8") bolt

B

 Base

C

  As long as possible.

D

 Vent

E

 Set deep in the ground

.

Max. 30 

Min. 10

Min. 360

(mm)

Fig. 2-4

Fig. 2-3

Fig. 2-5

Summary of Contents for PUHZ-BP HA

Page 1: ...R INSTALLER Air Conditioners PUHZ BP HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English ...

Page 2: ...the outdoor unit must be firmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock or fire may result When installing or moving the air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause press...

Page 3: ...xed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use a vacuum pump with a reverse flow check valve If the vacuum pump oil flows backward into the refrigerant lines refriger ant oil deterioration may result Use the following tools specifically designed for use w...

Page 4: ...uides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for BP125 BP250 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for BP125 BP250 models is 1000 mm or more When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm or mor...

Page 5: ...aks after connections are completed Apply refrigerating machine oil over the entire flare seat surface C Fig 4 1 Use the flare nuts for the following pipe size D Fig 4 1 When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the...

Page 6: ...door unit model Use the appropriate method to open the stop valves 1 Gas side Fig 4 6 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counter clockwise direction to open 2 Make sure that the stop valve is open comletely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 7 1 Remove the cap and turn the valve rod counterclockwise as far as it...

Page 7: ...eaker E Earth For Heater For Heater For Heater For Heater For Power BP170 BP250 only Fig 6 1 BP170 BP250 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it F Power supply terminal block L1 L2 L3 N G Indoor outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clampthe cables so that they do not contact the center of the service pane...

Page 8: ...it power supply 5 Min 4 Indoor unit Outdoor unit Cable length 50 m 3 4 Polar Cable length 80 m 3 6 Polar Indoor unit Outdoor unit earth 1 Min 2 5 Remote controller Indoor unit 2 0 3 Non polar Circuit rating Outdoor unit L1 N L2 N L3 N AC 220 230 240 V Indoor unit Outdoor unit S1 S2 AC 220 230 240 V Indoor unit Outdoor unit S2 S3 DC 24 V Remote controller Indoor unit DC 12 V 2 1 3 4 4 4 1 A breaker...

Page 9: ... 1 MΩ the compressor is faulty or the resis tance dropped due the accumulation of refrigerant in the compressor 3 After connecting the wires to the compressor the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accumulation of refrigerant in the com pressor Th...

Page 10: ...here is no need of wiring 2 A Outdoor unit B Indoor unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes after the refrigerant colle...

Page 11: ...11 Fig 2 11 Fig 2 13 Fig 2 14 Fig 2 16 Fig 2 17 Fig 2 10 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 12 Fig 2 15 Fig 2 18 Fig 2 9 ...

Page 12: ...00 8310 JAPAN BH79D068K03 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: