background image

50

•PUHY-P750YSHM-A(-BS)

Measurement 
location

1m

1m

10

20

30

40

50

60

70

80

90

63

125

250

500

1k

2k

4k

8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Octa

v

e

 band sound le

v

el (dB)

Approximate minimum
audible limit on
continuous noise

Standard

50/60Hz

Low

50/60Hz

63

125

250

500

1k

2k

4k

8k

dB(A)

Standard

75.0

68.0

64.5

60.0

56.5

53.0

49.5

43.0

63.5

Low Noise Mode

56.0

57.0

52.0

48.0

47.5

49.0

47.0

43.0

55.0

When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation 
from Low Noise Mode automatically in the case that the operation condition is severe.

50/60Hz
50/60Hz

Summary of Contents for PUHY-P250YHM-A

Page 1: ...Model PUHY P Y S HM A PFAV P VM E F DATA BOOK AIR CONDITIONING SYSTEMS ...

Page 2: ...r refrigerant leakage 98 General Cautions 1 Indoor Unit Line up 1 2 Temperature range 2 3 Notes on selecting equipments 3 1 Notes on using the Fresh Air Intake type units Indoor Unit 1 Specifications 5 1 Standard type 2 Fresh air intake type 2 External dimensions 7 1 Standard type 2 Fresh air intake type 3 Center of gravity 13 4 Electrical wiring diagram 14 5 Sound Pressure Levels 18 6 Vibration l...

Page 3: ... P250YHM A PUHY P750YSHM A Nominal conditions 1 2 are referable at the Specification sheet P600 20HP 56 0 50 0 PUHY P500YSHM A Model type Standard type Model size P250 P750 Nominal HP 10HP 30HP Nominal cooling cap 1 kW 25 0 71 0 Nominal heating cap 2 kW 28 0 80 0 Floor standing PFAV P VM E Connectable outdoor unit type PUHY P250YHM A PUHY P750YSHM A Nominal conditions 1 2 are referable at the Spec...

Page 4: ...re operated under such conditions cover the entire surface of all indoor units with insulating materials with a thickness of between 0 and 20 mm 13 16 in to prevent condensate from collecting Cooling Heating Note 2 Indoor temperature Wet bulb temperature 15 35 C 50 95 F Dry bulb temperature 0 20 C 32 68 F Outdoor temperature Dry bulb temperature 20 43 C 68 109 F Wet bulb temperature 4 15 5 C 24 60...

Page 5: ...e room temperature The unit will go into the forced Thermo OFF mode when the return air dry bulb temperature outside air temperature sensor reading is 21 C 70 F or below during cooling OR 20 C 68 F or above during heating The settable temperature range on the remote controller is as follows Cooling 19 30 C 66 86 F Heating 17 28 C 63 82 F Indoor temperature and humidity can fluctuate greatly depend...

Page 6: ...re reaches 6 C 43 F or above the units will resume operation in the selected mode The fan will stop when there is an error regardless of the outside temperature Operation OFF ON Operating the fan during the defrost cycle can cause cold outside air to be delivered into the room and it can also delay normal unit operation to be resumed after the defrost cycle is completed both of which can greatly d...

Page 7: ...31 0 29 9 30 8 29 3 28 2 31 1 29 6 28 5 2 37 3 36 6 2 5 9 5 7 6 5 6 2 6 0 Sirocco fan x 1 180 30 130 5 5 R410A Galvanized steel plate with polyester coating MUNSELL 5Y 8 1 or similar 1899 H x 1420 W x 635 D Over current protection 15 88 Brazed 28 58 Brazed 165 59 62 265 Indoor 10 to 25 degCWB Indoor 15 to 28 degCDB Outdoor 5 to 43 degCDB Outdoor 20 to 15 5 degCWB PFAV P750VM E PUHY P750YSHM A PUHY...

Page 8: ...occo fan x 1 90 110 170 2 2 R410A Galvanized steel plate with polyester coating MUNSELL 5Y 8 1 or similar 1899 H x 1420 W x 635 D Over current protection 15 88 Brazed 28 58 Brazed 165 50 53 248 Indoor 15 to 35 degCWB Indoor 0 to 20 degCDB Outdoor 20 to 43 degCDB Outdoor 4 to 15 5 degCWB PFAV P900VM E F PUHY P750YSHM A PUHY P350YHM A PUHY P400YHM A CMY Y200VBK2 80 0 Maximum 100 0 71 0 Maximum 80 0 ...

Page 9: ...space for installation work such as piping and wiring separately Notes 1 Be sure to wire the transmission line and power line separately 2 When the room in which the unit is installed is airtight the pressure in the room may become negative This may result in problems such as the door to becoming difficult to open etc To avoid these kinds of problems please ensure that a small amount of air is abl...

Page 10: ... as piping and wiring separately Supply air duct flange 3 1 2 4 6 5 Remote controller Front air inlet 7 Minimum necessary dimension 247 9 484 444 9 33 200 200 33 118 120 Notes 1 Be sure to wire the transmission line and power line separately 2 When the room in which the unit is installed is airtight the pressure in the room may become negative This may result in problems such as the door to becomi...

Page 11: ...ia some kind of small hole or vent 4 Connect by using the connecting pipes that are supplied Size on inside Size on inside 2 5 6 3 4 Size on inside 8 7 2 1 5 6 Air filter 1 2 5 6 1 Size on inside 476 56 439 606 30 12 476 110X4 440 18 20 ø4 3Holes 606 110X4 440 83 42 750 500 1000 400 580 100 875 810 740 450 220 150 112 493 994 741 70 35 10 1212 106 200X5 1000 599 106 300 195 715 25 30 750 106 1460 ...

Page 12: ...ase ensure that a small amount of air is able to ventilate the room via some kind of small hole or vent 8 8 Service for thermistor Service for motor pulley Service for fan pulley Service panel Secure the proper space for installation work such as piping and wiring separately 300 173 Rear air inlet duct flange 40 Rear air inlet duct flange 67 26 125 125 15 110 300 20 15 28 ø 3 Holes 1126 Supply air...

Page 13: ... dimension Secure the proper space for Indoor unit installation work such as piping and wiring separately Notes 1 Be sure to wire the transmission line and power line separately 2 When the room in which the unit is installed is airtight the pressure in the room may become negative This may result in problems such as the door to becoming difficult to open etc To avoid these kinds of problems please...

Page 14: ... via some kind of small hole or vent 4 Connect by using the connecting pipes that are supplied Size on inside Size on inside 2 5 6 3 4 Size on inside 8 7 2 1 5 6 Air filter 1 2 5 6 1 Size on inside 476 56 439 606 30 12 476 110X4 440 18 20 ø4 3Holes 606 110X4 440 83 42 750 500 1000 400 580 100 875 810 740 450 220 150 112 493 994 741 70 35 10 1212 106 200X5 1000 599 106 300 195 715 25 30 750 106 146...

Page 15: ...F P600 F PFAV P750 P900 F W X Y Z L 445 615 835 1774 X W Model L Y X Z PFAV P250VM E PFAV P500VM E PFAV P300VM E F PFAV P600VM E F 1234 1450 1234 1450 300 440 300 440 573 651 573 667 156 217 161 219 835 1144 825 1113 X Model PFAV P750VM E PFAV P900VM E F 1020 ...

Page 16: ...nal bed Power source terminal bed Fan motor Symbol Symbol explanation TB15 51F 52F LEV1 T ZNR F TB5 TB2 M Connector Defrost output CN33 Name Symbol LEV2 Electronic linear expan valve 2 2nd digit address set Name 2 3 1 3 1 3 CN33 T 52F ZNR F X06 1 1 1 CNT CND X4 2 1 2 1 1 M CN28 3 2 1 CN20 CN21 3 2 1 X4 CN29 CN3T CN60 CN31 R B TB6 LCD TB5 Shield 2 1 1 3 51F 52F X05 X04 7 2 1 CN3A M1 S M2 3 5 CN90 C...

Page 17: ... Indoor controller board No 2 3 1 1 2 3 4 5 6 SW14 SW12 SW11 Indoor Outdoor transmission line M1 S M2 2 1 CN2M CNP 1 3 CN28 1 2 X4 t t t TH21 TH22 TH23 2 1 2 1 CN21 2 1 CN20 CN29 CN3A 2 1 CN2M CNP 1 3 SW8 SW5 1 3 1 3 CN33 ZNR F X06 X05 X04 7 1 3 5 CND CN90 9 5 U 1 T CN3T 3 1 CNT 2 3 4 5 U 6 M 7 CN7V SWE t t 50 60Hz 380 400 415V 9 TH23 CN29 2 1 t M 6 5 4 3 2 1 SW4 X4 X2 52F X1 F1 SW7 SW2 6 5 4 3 2 ...

Page 18: ...rrent relay Fan motor Connector Fan failure Switch For trial run of fan Switch For mode selection Switch For trial run Switch For four stages demand selection Switch For model selection Switch For mode selection Switch For capacity code Switch For mode selection Switch For model selection Switch Connection No set Switch 1st digit address set Thermistor Piping temp detection gas SW7 SW1 SW14 SW12 S...

Page 19: ...explanation MA Remote controller terminal bed M R B LCD TB2 TB5 TB15 ZNR T LEV1 Contactor Fan motor 52F 51F Over current relay Fan motor CN33 Connector Defrost output Thermistor Piping temp detection gas Thermistor Piping temp detection liquid Thermistor Outdoor temp detection Switch For model selection SW7 SW1 SW14 SW12 SW11 SW4 SW5 SW8 Switch For model selection Switch Connection No set Switch F...

Page 20: ...4000 8000 NC 70 NC 60 NC 50 NC 30 NC 20 NC 40 OCTAVE BAND PRESSURE LEVEL dB 0 dB 20µPa 1m 1m Measurement location Power sorce 3N 380 400 415V 50 60Hz Note The measuring point is the 1m from the bottom of the unit 1m from the front of the unit 38 8000Hz 62 dB A 46 5 4000Hz 54 2000Hz 57 1000Hz 57 5 500Hz 60 250Hz 69 125Hz 77 5 33 59 41 5 49 53 56 56 5 65 73 5 63Hz 50Hz 60Hz 50Hz 60Hz NC Curve OCTAVE...

Page 21: ...70 NC 60 NC 50 NC 30 NC 20 NC 40 OCTAVE BAND PRESSURE LEVEL dB 0 dB 20µPa 1m 1m Measurement location 1m 1m Power sorce 3N 380 400 415V 50 60Hz Measurement location Note The measuring point is the 1m from the bottom of the unit 1m from the front of the unit 25 5 8000Hz 48 5 dB A 32 4000Hz 37 5 2000Hz 41 1000Hz 44 5 500Hz 52 250Hz 56 5 125Hz 59 5 25 5 48 5 29 5 39 40 43 5 52 5 56 5 61 5 63Hz 50Hz 60...

Page 22: ...0 NC 70 NC 60 NC 50 NC 30 NC 20 NC 40 OCTAVE BAND PRESSURE LEVEL dB 0 dB 20µPa 1m 1m Measurement location Power sorce 3N 380 400 415V 50 60Hz Note The measuring point is the 1m from the bottom of the unit 1m from the front of the unit 32 8000Hz 57 dB A 41 4000Hz 43 5 2000Hz 51 5 1000Hz 52 5 500Hz 58 250Hz 67 125Hz 70 32 57 41 43 5 51 5 52 5 58 67 70 63Hz 50Hz 60Hz 50Hz 60Hz NC Curve OCTAVE BAND CE...

Page 23: ...21 6 Vibration levels PFAV indoor unit Concrete Measurement location Leg PFAV Unit 10cm 20cm Vibration Levels dBA 40 or less Model PFAV P250 500 750VM E PFAV P300 600 900VM E F ...

Page 24: ...2 3 15 20 21 22 23 16 17 18 19 Standard 50Hz Internal resistance Airflow rate m3 min Total static pressure Pa Standard 60Hz 110 70 75 80 85 90 95 100 105 100 200 300 400 500 700 900 800 600 0 23 22 21 20 19 18 17 16 2 2kW 14 13 12 11 10 9 8 7 6 5 4 3 2 1 15 Internal resistance Total static pressure Pa Airflow rate m3 min PFAV P250VM E ...

Page 25: ...1 6 9 6 9 7 0 7 0 6 8 6 9 6 9 6 7 6 8 6 9 6 8 Rotational speed rpm No Outside diameter ø Outside diameter A ø Nominal Diameter B ø Deflection force N Amount of deflection mm 14 7 15 1 15 3 15 6 15 8 14 9 14 7 15 0 15 3 15 6 16 0 14 5 15 3 15 7 16 1 16 5 16 3 16 6 15 9 16 6 15 7 16 9 17 5 6 9 7 0 7 0 7 0 7 1 6 9 6 9 6 9 7 0 7 0 7 1 6 8 6 9 6 9 7 0 7 0 6 8 6 9 6 8 6 9 6 5 6 6 6 7 Slide peace Rotatio...

Page 26: ...4 4 1 4 4 1 2 4 3 4 0 0 4 0 8 1 1 1 5 1 9 2 3 2 6 3 0 3 4 3 8 4 1 4 5 4 9 5 3 5 6 6 0 6 4 6 8 7 1 150 0 148 8 147 5 146 3 145 1 143 9 142 6 141 4 140 2 139 0 137 7 136 5 135 3 134 1 132 8 131 6 130 4 129 1 127 9 126 7 Pulley M8 keyway e 12 5 k 5 5 o 9 5 ko 12 5 m Rz 3 2 Rz 3 2 Rz 12 5 B d m Pulley nominal diameter Belt dm Pulley nominal diameter 201 dm dm 126 34 36 38 Rz 6 3 Rz 6 3 R z 3 2 R z 3 2...

Page 27: ...800 2 3 1 4 5 6 7 8 9 10 5 5KW Standard 50Hz Internal resistance Airflow rate m3 min Total static pressure Pa Standard 60Hz Internal resistance Airflow rate m3 min Total static pressure Pa 700 600 500 400 300 200 100 240 230 220 210 200 190 180 170 160 150 0 140 800 3 2 1 5 6 7 8 9 10 4 5 5KW ...

Page 28: ...38 38 38 38 38 41 3 42 42 42 42 42 42 42 42 42 10 10 10 10 10 10 10 10 10 10 Outside diameter A ø Nominal Diameter B ø Bore E ø C ø D ø F mm G mm V belt H mm in Motor 5 5kW 1450rpm 50Hz Motor pulley Fan pulley 1 2 3 4 5 6 7 8 9 10 1105 1059 1005 946 894 847 798 753 701 660 224 190 200 212 224 236 250 280 300 300 235 201 211 223 235 247 261 291 311 311 205 171 181 193 205 217 231 261 281 281 80 80 ...

Page 29: ...0 16 5 11 0 H outer center M8 Rz 6 3 Rz 3 2 Rz 6 3 Rz 6 3 19 Rz 3 2 Rz 3 2 keyway 9 5 5 5 12 5 59 44 12 5 C R z 3 2 R z 3 2 Rz 6 3 Rz 6 3 D A d Pulley outside diameter B dm Pulley nominal diameter 11 Belt dm Pulley nominal diameter 201 dm dm 160 34 36 38 161 dm 200 E G F ...

Page 30: ... 400 300 200 100 Standard 50Hz Internal resistance Airflow rate m3 min Total static pressure Pa Standard 60Hz Internal resistance Airflow rate m3 min Total static pressure Pa 7 5kW 1 2 3 4 5 6 7 8 9 10 11 13 12 100 200 300 400 500 600 700 800 900 1000 1100 0 220 240 260 280 300 320 340 PFAV P750VM E ...

Page 31: ...t H mm in Motor 7 5kW 1450rpm 50Hz Motor pulley Fan pulley 1 2 3 4 5 6 7 8 9 10 11 12 13 1178 1152 1100 1056 992 944 900 846 788 750 700 656 591 315 243 300 315 300 315 300 300 300 315 400 400 400 326 254 311 326 311 326 311 311 311 326 411 411 411 296 224 281 296 281 296 281 281 281 296 381 381 381 90 70 90 90 90 90 90 90 90 90 90 90 90 32 32 32 32 32 32 32 32 32 32 32 32 32 36 36 36 36 36 36 36 ...

Page 32: ...0 16 5 11 0 H outer center M8 Rz 6 3 Rz 3 2 Rz 6 3 Rz 6 3 19 Rz 3 2 Rz 3 2 keyway 9 5 5 5 12 5 59 44 12 5 C R z 3 2 R z 3 2 Rz 6 3 Rz 6 3 D A d Pulley outside diameter B dm Pulley nominal diameter 11 Belt dm Pulley nominal diameter 201 dm dm 160 34 36 38 161 dm 200 E G F ...

Page 33: ...1 10 9 7 8 5 2 4 3 1 23 21 6 24 25 Standard 50Hz Internal resistance Airflow rate m3 min Total static pressure Pa Internal resistance Airflow rate m3 min Total static pressure Pa Standard 60Hz 36 54 1 5kW 45 40 50 600 800 700 500 400 300 200 100 0 22 20 23 21 19 18 14 17 16 15 13 12 11 10 9 8 7 6 5 4 2 3 1 ...

Page 34: ...Rotation number Bore E ø Bore E ø C ø D ø F mm G mm F mm G mm V belt H mm in Motor 1 5kW 1450rpm 50Hz Motor pulley Fan pulley 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 1596 1547 1505 1462 1419 1376 1337 1302 1254 1218 1182 1135 1094 1055 1017 979 941 912 877 825 783 753 729 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 149 4 1 1 2 2 1 4 3...

Page 35: ...5 3 5 6 6 0 6 4 6 8 7 1 140 0 138 8 137 5 136 3 135 1 133 9 132 6 131 4 130 2 129 0 127 7 126 5 125 3 124 1 122 8 121 6 120 4 119 1 117 9 116 7 Fixed disc must be See p 40 for How to choose the pulley placed on the motor side Pulley M8 keyway e 10 k 4 5 o 8 ko 9 2 m Rz 3 2 Rz 3 2 Rz 12 5 B d m Pulley nominal diameter Belt dm Pulley nominal diameter 201 dm 36 38 Rz 6 3 Rz 6 3 R z 3 2 R z 3 2 C A d ...

Page 36: ...tic pressure Pa Standard 60Hz 72 108 90 80 100 0 200 400 600 500 300 100 700 12 11 10 9 8 7 6 5 4 3 2 1 13 2 2KW Internal resistance Airflow rate m3 min Total static pressure Pa 72 108 90 80 100 0 200 400 600 500 300 100 2 2KW 700 10 9 8 7 6 5 4 3 1 2 PFAV P600VM E F ...

Page 37: ... 28 28 28 28 28 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 8 8 8 8 8 8 8 8 8 8 8 8 8 Outside diameter A ø Nominal Diameter B ø Bore E ø C ø D ø F mm G mm V belt H mm in Motor 2 2kW 1450rpm 50Hz Motor pulley Fan pulley 1 2 3 4 5 6 7 8 9 10 1023 964 912 865 816 771 728 678 646 572 200 212 224 236 250 280 280 300 315 355 211 223 235 247 261 291 291 311 326 366 181 193 205 217 23...

Page 38: ...e 12 5 k 5 5 o 9 5 ko 12 5 m Rz 3 2 Rz 3 2 Rz 12 5 B d m Pulley nominal diameter Belt dm Pulley nominal diameter 201 dm dm 160 34 36 38 Rz 6 3 Rz 6 3 R z 3 2 R z 3 2 C A d Pulley outside diameter 25 40 11 e k k m Rz 6 3 Rz 6 3 Rz 3 2 D E G F 161 dm 200 40 16 5 11 0 H outer center ...

Page 39: ...3 1 2 4 5 6 7 8 10 11 12 9 3 7kW 120 1000 900 800 700 600 500 400 300 200 100 100 140 0 96 144 120 1000 900 800 700 600 500 400 300 200 100 100 140 0 96 144 Standard 60Hz Internal resistance Airflow rate m3 min Total static pressure Pa 2 1 3 4 5 6 8 9 13 10 11 12 14 3 7kW 7 PFAV P900VM E F ...

Page 40: ... 71 71 71 63 71 71 63 63 28 28 28 28 28 28 28 28 28 28 28 28 28 28 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 31 3 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Outside diameter A ø Nominal Diameter B ø Bore E ø C ø D ø F mm G mm V belt H mm in Motor 3 7kW 1450rpm 50Hz Motor pulley Fan pulley 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1056 1025 944 889 833 778 750 694 656 634 613 591 547 500 315 315 315...

Page 41: ...0 16 5 11 0 H outer center M8 Rz 6 3 Rz 3 2 Rz 6 3 Rz 6 3 19 Rz 3 2 Rz 3 2 keyway 9 5 5 5 12 5 59 44 12 5 C R z 3 2 R z 3 2 Rz 6 3 Rz 6 3 D A d Pulley outside diameter B dm Pulley nominal diameter 11 Belt dm Pulley nominal diameter 201 dm dm 160 34 36 38 161 dm 200 E G F ...

Page 42: ...r pulley Fan pulley 23 9 25 3 23 3 24 2 24 2 25 6 26 4 28 4 29 6 31 6 32 4 34 4 35 5 5 0 5 1 4 9 5 1 4 8 5 1 4 8 4 9 4 9 4 8 4 9 5 0 4 7 Deflection force Amount of Deflection How to choose the pulley EXAMPLE Indoor unit PFAV P750VM E 50Hz Required external static pressure 600 Pa Required air flow rate 250m3 min 7 5kW 1 3 4 5 6 9 11 2 7 8 13 12 10 340 320 300 280 260 240 220 0 1100 1000 900 800 700...

Page 43: ...486 1750 Air outlet Note 1 The external static pressure in the plenum chamber is 30 Pa Note 2 The plenum chamber is not interchangeable with the Fresh air intake type Note 3 Largely changing the louver angle may result in condensing or capacity shortage of the unit For P750 indoor unit PAC CC87PL E For P250 indoor unit PAC CC83PL E For P500 indoor unit PAC CC85PL E mm mm mm Keep the louver angle w...

Page 44: ...opper pipe pipe in pipe structure Auto defrost mode Reversed refrigerant circle WKB94G533 Installation Manual Refrigerant conn pipe Outdoor Twinning Kit CMY Y100VBK2 WKE94C140 WKE94C140 Defrosting method Auto defrost mode Reversed refrigerant circle Drawing External WKB94G531 Wiring WKE94C140 Standard attachment Document Installation Manual Accessory Refrigerant conn pipe Optional parts Remark Det...

Page 45: ...rk 2 The detachable leg can be removed at site 3 At brazing of pipes wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 120 C Accessories Connecting pipe Gas Elbow ID25 4XOD25 4 P250 1pc Pipe ID25 4XOD22 2 P250 1pc Liquid Pipe ID9 52XOD9 52 P250 1pc 1 1 Connect by using the connecting pipes for bottom piping and front piping that are suppl...

Page 46: ...ugh hole Bottom through hole Front through hole Front through hole Bottom through hole Front through hole 102X72 Knockout hole 150X94 Knockout hole 65 or 40 Knockout hole 52 or 27 Knockout hole 65 Knockout hole 34 Knockout hole 12 7 Brazed PUHY P400YHM PUHY P350YHM 172 158 B Gas A Liquid Gas Liquid front and back 2 points Note 2 1 1 Connect by using the connecting pipes for bottom piping and front...

Page 47: ...id Liquid Outdoor unit 2 920 760 30 920 60 1650 1710 Intake air Outdoor unit 2 Outdoor unit 1 Discharge air Intake air Intake air Left view To indoor unit Front view c d b a f e Gas Twinning pipe optional parts Liquid Twinning pipe optional parts To indoor unit Twinning pipe connection size PUHY P500YSHM A BS PUHY P250YHM A BS PUHY P250YHM A BS Package unit name Component unit name Outdoor Twinnin...

Page 48: ...a Gas Liquid Indoor unit Twinning pipe Outdoor Twinning Kit optional parts Outdoor unit 2 Outdoor unit 1 Component unit name Package unit name Twinning pipe connection size 1650 60 1710 760 30 1220 1220 Front view Left view Detachable leg Note 2 Intake air Discharge air Outdoor unit 2 Outdoor unit 1 Intake air Intake air d c f e b a To indoor unit Gas Twinning pipe optional parts Liquid Twinning p...

Page 49: ... P250YHM A Unit mm Unit mm 760 80 Y 724 1470 Z 60 920 X 760 Model X Y Z 334 329 652 PUHY P250YHM A BS 1060 80 Y 724 1470 Z 60 1220 X 760 Model X Y Z 440 329 630 440 329 630 PUHY P350YHM A BS PUHY P400YHM A BS PUHY P350 P400YHM A ...

Page 50: ...8 C9 C10 C4 C1 C6 Power Source 3N 50 60Hz 380 400 415V N L3 L2 L1 TB1 N L3 L2 L1 L F4 AC250V 6 3A T black white red 3 1 CN3 green TB24 N TB23 L3 TB22 L2 TB21 L1 CN1B 4 1 3 1 CN1A U U U F1 F2 F3 AC250V 6 3A T U Z4 DSA CN2 6 5 3 1 Noise Filter U ZNR01 U 3 1 CN5 red 3 CN4 blue 1 4 7 1 CNINV CNVDC 4 1 FAN Board F01 DC700V 4A T C630 C631 R631 R630 IPM CN18V blue CN4 red CN5 2 1 1 3 1 2 2 3 4 1 CN21 blu...

Page 51: ...ous noise Standard 50 60Hz Low 50 60Hz 63 125 250 500 1k 2k 4k 8k dB A Standard 59 0 62 0 60 0 54 0 50 5 46 0 41 0 35 0 57 0 Low Noise Mode 58 0 53 5 44 0 39 0 36 5 32 5 31 0 24 5 44 0 When Low Noise Mode is set the A C system s capacity is limited The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe 50 60Hz 50 60Hz 63 125...

Page 52: ...m audible limit on continuous noise Standard 50 60Hz Low 50 60Hz 63 125 250 500 1k 2k 4k 8k dB A Standard 75 0 68 0 64 5 60 0 56 5 53 0 49 5 43 0 63 5 Low Noise Mode 56 0 57 0 52 0 48 0 47 5 49 0 47 0 43 0 55 0 When Low Noise Mode is set the A C system s capacity is limited The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is sev...

Page 53: ...Local brazing Pipe cover 15 88 19 05 15 88 15 88 19 05 15 88 Note 2 191 244 85 115 Distributer Dot dashed part 28 58 28 58 28 58 28 58 31 75 Local brazing Dot dashed part Pipe cover 162 585 337 Note 2 34 93 Distributer 503 The angle of the branch pipe is within against the ground 2 Use the attached pipe to braze the port opening of the distributer 3 Pipe diameter is indicated by inside diameter No...

Page 54: ... Indoor Temperature CWB Indoor Temperature CWB Ratio of cooling capacity Ratio of power input P500 Cooling input Cooling capacity 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 5 0 5 10 15 20 25 30 35 40 45 24 22 20 18 16 15 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 5 0 5 10 15 20 25 30 35 40 45 24 22 20 18 16 15 Outdoor temperature CDB Ratio of cooling capacity Outdoor temperature CDB Indoor Temperature CWB Indoor Te...

Page 55: ...rature CDB Indoor Temperature CDB Ratio of power input P500 Heating input Heating capacity 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 20 15 10 5 0 5 10 15 15 20 25 27 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 20 15 10 5 0 5 10 15 15 20 25 27 Outdoor temperature CWB Ratio of heatling capacity Outdoor temperature CWB Indoor Temperature CDB Indoor Temperature CDB Ratio of power input P750 Heating input Heating ca...

Page 56: ...nt length Actual piping length to the indoor unit 0 42 number of bent on the piping m Piping equivalent length m Cooling capacity correction factor Piping equivalent length m Heating capacity correction factor P500 P600 E F Heating How to obtain piping equivalent length Cooling Equivalent length Actual piping length to the indoor unit 0 5 number of bent on the piping m 0 65 0 70 0 75 0 80 0 85 0 9...

Page 57: ...eating Cooling 1 Solid line indicates capacity correction factor 2 Broken line indicates input correction factor Airflow rate m3 min Capacity input correction factor Airflow rate m3 min Capacity input correction factor P750 Heating Cooling 1 Solid line indicates capacity correction factor 2 Broken line indicates input correction factor 0 90 1 00 1 10 210 230 250 270 290 310 330 350 0 90 1 00 1 10 ...

Page 58: ...0 1 00 50 60 70 80 90 100 Ratio of heating capacity 2 Cooling input correction factor Ratio of cooling capacity 1 Heating input correction factor P500 P600 E F Heating Cooling 1 Cooling capacity devided by maximum cooling capacity 2 Heating capacity devided by maximum heating capacity 3 in figure indicates P500 type nominal input factor at nominal capacity 4 in figure indicates P600 F type nominal...

Page 59: ...160 170 180 190 200 210 220 230 240 Airflow rate m3 min Bypass factor Airflow rate m3 min Bypass factor P750 P300 E F 0 00 0 10 0 20 0 30 0 00 0 10 0 20 0 30 0 40 210 230 250 270 290 310 330 350 35 40 45 50 55 Airflow rate m3 min Bypass factor Airflow rate m3 min Bypass factor P600 E F P900 E F 0 00 0 10 0 20 0 30 70 80 90 100 110 0 00 0 10 0 20 0 30 95 105 115 125 135 145 ...

Page 60: ... temperature Reset filter 1 When the local remote controller inactivation command is received from the master system controller is displayed Indoor unit intake temperature Prohibition permission of specified mode Cooling prohibited heating prohibited cooling heating prohibited Measures the intake temperature of the indoor unit when the indoor unit is operating Error When an error is currently occu...

Page 61: ...e sites where strong winds blow 4 With strength to bear the weight of the unit 5 Drain flow from the unit is cared at heating mode 6 Enough space for installation and service as shown at 2 7 Avoid the sites where acidic solutions or chemical sprays sulfur series are used frequently 8 The unit should be secure from combustible gas oil steam chemical gas like acidic solution sulfur gas and so on ...

Page 62: ...er to the Installation Manual when installing units on an installation base In case of collective installation When multiple units are installed adjacent to each other secure enough space to allow for air circulation and walkway between groups of units as shown in the figures below At least two sides must be left open As with the single installation add the height that exceeds the height limit h t...

Page 63: ... be attempted Use protective pads to keep the ropes from scratching the panels on the unit Products weighing more than 20 kg 45 LBS should not be carried alone Do not carry the product by the PP bands T o avoid the risk of injury do not touch the heat exchanger fins Plastic bags may pose a risk of choking hazard to children Tear plastic bags into pieces before disposing of them When lifting and tr...

Page 64: ...5 3 16 5 23 32 5 3 16 5 23 32 94 3 23 32 Mounting pitch Refrigerant service valve liquid Mounting pitch 2X2 14X20 Oval hole Refrigerant service valve gas 271 216 18 80 80 1060 41 3 4 18 23 32 23 32 23 32 23 32 28 13 32 28 5 8 28 13 32 28 5 8 301 83 131 760 29 15 16 145 145 5 23 32 Bottom view 724 721 727 3 5 32 3 5 32 3 5 32 3 5 32 7 11 32 8 17 32 11 7 8 3 9 32 10 11 16 5 29 32 9 29 32 3 9 32 8 23...

Page 65: ...r of the angle bracket at the base of the unit shown in the figure below is securely supported Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm 1 3 16 in This unit is not designed to be anchored with post installation type anchor bolts although by adding fixing brackets anchoring with such type of anchor bolts becomes possible Individual in...

Page 66: ...f pipe connected in front of the twinning pipe must be 500 mm 19 inch or longer Connect the field piping so that the length of the straight part of pipe connected in front of the twinning pipe can be 500 mm 19 inch or longer If the length is less than 500 mm 19 inch it will cause damage to the unit When installing the twinning kit in a higher position than the outdoor unit base make sure that the ...

Page 67: ... connecting the pipes between the outdoor units CAUTION The length of the straight pipe must be 500mm or longer If not it may cause improper operation Field piping Field piping Twinning kit The length of the straight pipe must be 500 mm 19 inch or longer PUHY P500YSHM A ...

Page 68: ... angle steel etc and designed so that snow and wind slip through the structure If frame base is too wide snow will be accumulated on it 2 Install unit so that wind will not directly lash against openings of inlet and outlet ducts 3 Build frame base at customer referring to this figure Material Galvanized steel plate 1 2T Painting Overall painting with polyester powder Color Munsell 5Y8 1 same as t...

Page 69: ...site carefully to minimize the effect of winds To install a unit in a place where the wind always blows from the same direction install the unit so that the outlet faces away from the direction of the wind Wind Install the outdoor unit where seasonal winds do not blow directly against the unit such as behind a building Install the outdoor unit to avoid having seasonal winds against the front of ai...

Page 70: ...e of oil and drain water can corrode the copper pipe and seriously shorten its life 12 Corrosive gasses e g sulfuric gas that are generated in a place where food items are processed and or stored can damage the indoor unit and seriously shorten its life Caution If the units are operated for a long time at the dew point temperature of 23 C 73 F or more condensate may collect and drip from the indoo...

Page 71: ...space if a duct is connected 300 P300 500 or more P600 100 or more Front space PFAV P250 500VM E Unit mm Optional plenum chamber Front space Power cable hole 380V or more Wire hole for the device power supply Through hole for the remote controller wiring to outdoor unit Wood base Refrigerant pipes Drain pipe 300 85 or more P250 800 or more P500 1000 or more 50 or more 100 or more P250 500 or more ...

Page 72: ...iquid 1000 or more 750 or more 500 or more 400 or more 85 or more Select a solid surface and install the unit on a wood base at least 8 5 cm in thickness to allow for proper discharge of drain water and to prevent vibration from the air conditioning units from being transmitted to the floor Secure additional clearance space for piping and wiring installation ...

Page 73: ...ion 71 3 Installing the Indoor Unit CAUTION Properly dispose of packing materials Pallets and the nails on the pallets can pose the risk of injury Plastic bags can pose suffocation and choking hazards keep out of the reach of children Tear the plastics bags before disposing of them CAUTION Exercise caution when transporting units Products weighing 20 kg 45 lbs or more should not be carried by one ...

Page 74: ...remove the panel 1 Loosen the two securing screws on the bottom front panel pull the front panel forward and remove the panel by pulling the panel up and forward 2 Disconnect the remote controller connector A in the figure below Be sure to disconnect the connector before removing the top front panel to prevent the remote controller cable from being damaged 3 Remove the two fixing screws on the top...

Page 75: ... run is completed check the setscrew for looseness Note Check that the desired rotation speed is in the operating range as indicated in the fan performance diagram If the rotation speed exceeds the operating range the overcurrent relay on the fan will trip Important notes on pulleys and pulley belts CAUTION Figure 2 Adjusting the horizontal alignment of the variable width pulley Figure 1 Variable ...

Page 76: ...ange as shown in the table in 7 3 After the belt has been broken in on the pulley after 24 to 28 hours of operation check the belt for looseness and adjust the belt tension as specified in step 2 above as necessary When setting the tension for a new belt set it to a value 1 15 times the deflection force W 4 After the initial adjustment of the belt as described in step 3 above readjust the belt ten...

Page 77: ...tems to be checked during test run Check for abnormal sounds and water leakage after test run a Remove the decoration panels 1 through 6 in that order b Remove the fan block fixing screws located in the positions as shown in the figure and pull the fan block 7 forward to remove it Please note that the fan block on the P500 model weighs 118 kg 261 lbs P600 F model weighs 93kg 205 lbs c Remove the b...

Page 78: ...main unit referring to the figures in the next page a Remove filter plates 1 2 screws are attached each on the right and left side of the heat exchanger block and take out the filter b Remove air inlet flanges 23 and then decoration panels 4 through 9 in number order c Cut off the part of the charge pipe connected to the field piping to reduce internal pressure Then debraze the piping part shown i...

Page 79: ...stors back on with their wirings properly reconnected and fixed 3 Do not compress the unit during separation or transportation After unit transportation or reassembling check that the fan parts pulley fan bearing have no loosen screws and pulleys are in proper position so that the V belt will not be damaged 4 Sound and water leakage check Check for abnormal sounds and water leakage after test run ...

Page 80: ...l Pulley Outlet Material Alloyed hot dip galvanized steel sheet Fresh air intake type only Intake duct flange PFAV P500VM E PFAV P600VM E F Material Hot dip galvanized steel sheet Rear panel Material Coil phosphorus deoxidized copper Fins aluminum Indoor heat exchanger Material Hot dip galvanized steel sheet Outlet Siroccofan Material Alloyed hot dip galvanized steel sheet Material Alloyed hot dip...

Page 81: ...heet Fan motor Material Hot dip galvanized steel sheet Fan Material Alloyed hot dip galvanized steel sheet Front panel upper Remote controller Terminal block for transmission V belt Drain pan F Material Hot dip galvanized steel sheet Control box Terminal Linear expansion valve Scroll dumper Air filter Material Alloyed hot dip galvanized steel sheet Drain pan Material Hot dip galvanized steel sheet...

Page 82: ... of R410A compared to R22 the flare connection should follow dimensions mentioned below so as to achieve enough the air tightness For pipe sized ø19 05 3 4 for R410A air conditioner choice of pipe type is up to you Size mm Size inch Radial thickness mm Pipe type ø1 4 0 8 ø3 8 0 8 ø1 2 0 8 Type O Type O Type O Type O Type O ø5 8 ø3 4 ø3 4 ø7 8 1 0 1 0 1 0 Type 1 2H or H Type 1 2H or H Type 1 2H or ...

Page 83: ... IU H OU under IU Table1 2 1 2 Bent equivalent length M M m bent ft bent Outdoor Model PUHY P250 0 42 1 38 Table1 2 1 1 Piping length m ft Max length Piping in the figure Item Max equivalent length A Height between OU and IU OU above IU Height between OU and IU OU under IU OU Outdoor Unit IU Indoor Unit 190 623 165 541 Farthest IU from OU L1 H H 50 164 40 131 mm in Outdoor Pipe Gas Pipe Liquid PUH...

Page 84: ... branch joint and outdoor unit exceeds 2 m provide at rap at a distance 2 m or less from the branch joint OK NG OU OU IU max Table1 2 2 2 Bent equivalent length M M m bent ft bent Outdoor Model PUHY P500 0 50 1 64 PUHY P750 0 70 2 29 Table1 2 2 1 Piping length m ft Max length Piping in the figure Item Max equivalent length A Height between OU and IU OU above IU Height between OU and IU OU above IU...

Page 85: ...0kg 9 0kg Total length of ø12 7 liquid pipe x 0 12 m x0 12 kg m P250 model 11 5kg P350 model 11 5kg P400 model Outdoor unit model Charged amount Total length for ø15 88 each pipe size ø9 52 C 2m A B 5m 2x0 2 5x0 06 5 0 5 7kg This yields the following result Total length of ø9 52 liquid pipe x 0 06 m x0 06 kg m Total length of ø6 35 liquid pipe x 0 024 m x0 024 kg m P250 P300 F P500 P600 F 8 0kg P7...

Page 86: ... 200m in length while ME R C transmission cable 0 3 1 25mm2 must be less than 10m in length But transmission cable to the ME R C can be extend using a M NET cable 1 25mm2 when the length is counted in the M Net length Both Compact MA and ME R C transmission cables size 0 75 1 25mm2 in thickness 6 MA remote controller and ME remote controller should not be grouped together 7 If using 1 or 2 main su...

Page 87: ...25mm2 must be less than 200m in length while ME R C transmission cable 0 3 1 25mm2 must be less than 10m in length But transmission cable to the ME R C can be extend using a M NET cable 1 25mm2 when the length is counted in the M Net length Both Compact MA and ME R C transmission cables size 0 75 1 25mm2 in thickness 6 MA remote controller and ME remote controller should not be grouped together 7 ...

Page 88: ... If connections are not fixed firmly heating or fire may result Be sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Caution Some installation sites may require attachment of an earth leakage breaker for the inverter If no earth leakage breaker is installed there is a danger of electric shock Do not use anyth...

Page 89: ... a noise source is located near the unit place the unit as far away from the noise source as possible to reduce noise interference 2Remote controller wiring Cable type Maximum total transmission line length Type Number of cores Cable size MA remote controller 2 core cable VCTF VCTFK CVV CVS VVR VVF VCT The use of cables that are 0 75 mm2 AWG 18 or smaller in diameter is recommended for easy handli...

Page 90: ...S Note 2 refrigerant circuit system OC and OS are differentiated automatically Note 3 Centralized controller TR SC 0 201 to 250 Any address within the address range on the left 000 System remote controller SR SC 201 to 250 Any address within the address range on the left 201 Schedule timer System M NET compatible ST SC 201 to 250 Any address within the address range on the left 202 controller ON O...

Page 91: ...89 4 An Example of a System to which an MA Remote Controller is connected P750 P900 F models only ...

Page 92: ...90 ...

Page 93: ...91 L2 L31 L4 L32 200m 656ft ...

Page 94: ...indoor unit can be set with the DIP SW SW1 9 10 on the unit Operation recovery after power failure Function Setting SW1 Note 4 Power reset Notes 1 2 and 3 Automatic recovery after power failure Note 3 Note 1 Do not turn off the power to the outdoor unit Turning off the power to the outdoor unit cuts of the power to the crankcase heater and this may lead to compressor failure when the operation is ...

Page 95: ...93 3 Emergency Operation Mode ...

Page 96: ...94 ...

Page 97: ...or units 1 Various types of control using input output signal connector on the outdoor unit various connection options 6 Take out signals from the outdoor unit that is designated as OC if multiple outdoor units exist in a single system ...

Page 98: ...96 ...

Page 99: ...97 ...

Page 100: ...ensor At 0 3m height from the floor Fresh air supply fan Indoor space Floor Fig 6 4 Fresh air supply and refrigerant shut off upon sensor action Note 1 Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens Note 2 In principle MITSUBISHI ELECTRIC requires proper piping design installation and air tight testing after installation to av...

Page 101: ...DATA BOOK PUHY P Y S HM A PFAV P VM E F Issued in Jul 2009 MEE08K100 Printed in Japan New publication effective Jul 2009 Specifications subject to change without notice ...

Reviews: