–76–
b
Check the refrigerant volume by self-diagnosis using the LED.
Set the self-diagnosis switch (SW1) as shown below and check the past information (history) concerning the
refrigerant volume.
Set SW1 as shown in he figure at right.
If LD8 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger-
ant overcharge (1500).
3
Additional Refrigerant Charge Volume
At the time of shipping from the factory, the outdoor unit is charged with the amount of coolant shown in the follow-
ing table, but since no extension piping is included, please carry out additional charging on-site.
Outdoor Unit Model Name
PU(H)Y-200YMF-C PU(H)Y-P200YMF-C PU(H)Y-250YMF-C PU(H)Y-P250YMF-C
Refrigerant Charge Volume
6.5kg
7.0kg
8.0kg
8.5kg
Calculation Formula
Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length (units: m).
Additional Refrigerant Volume
(kg) = (0.12
×
L
1
) + (0.06
×
L
2
) + (0.024
×
L
3
) +
α
L
1
:
Length of
ø
12.7 liquid pipe (m)
L
2
:
Length of
ø
9.52 liquid pipe (m)
L
3
:
Length of
ø
6.35 liquid pipe (m)
α
:
refer to the calculation table.
In the calculation results, round up fractions smaller than 0.01 kg. (Example: 18.54 kg
→
18.6 kg)
(
α
Calculation Table)
Total Capacity of
α
Connected Indoor Units
~90
1.0 kg
91 ~180
1.5
181 ~370
2.0
Caution : (PUHY-P200·250YMF-C)
When charging with refrigerant, be sure to charge from the liquid side. If charging from the gas side, it will cause
the refrigerant composition to change inside the unit and the composition of the refrigerant remaining in the
canister will also change.
for PU(H)Y-(P)200·250YMF-C
1 2 3 4 5 6 7 8 9 10
ON