61
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Display as an outdoor
capacity code
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting advice
Indoor unit piping temperature / LIQUID
(TH2)
Indoor 1
– 39~88
Code
display
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
8~39
Capacity
P71
P100
P125
P140
Code
14
20
25
28
Setting details
●
The tens digit (Total display for applied setting)
●
The units digit
H·P / Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 : Single phase 2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : High humidity region
(Example) When switching cooling and heat pump,
three phase, defrosting (normal)
“20”
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor unit piping temperature / LIQUID
(TH2)
Indoor 2
– 39~88
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
When no indoor unit, “00” is displayed.
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
When no indoor unit, “00” is displayed.
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns)
When no indoor unit, “00” is displayed.
:
:
:
8~39
Indoor unit piping temperature / LIQUID
(TH2)
Indoor 3
– 39~88
Indoor unit piping temperature / LIQUID
(TH2)
Indoor 4
– 39~88
OC379F