33
9-2. FUNCTION OF DIP SWITCH
The black square (■) indicates a switch position.
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW1
Function
Selection
1
Thermistor
<Room temperature
detection> position
Built-in remote
controller
Indoor unit
Under
suspension
Indoor controller board
ON
OFF
ON
OFF
1 2 3 4 5 6 7 8 9 0
<Initial setting>
*
1
Fan operation at heating mode
*
2
Heat thermo-ON is operating.
*
3
Refer to the <Table A> below.
2
Filter clogging
detection
Provided
Not provided
3
Filter cleaning
2,500h
100h
4
Fresh air intake
Effective
Not effective
5
Switching remote
indication
Thermo-ON signal
display
Indicating fan
operation ON/OFF
6
Humidifier control
Always operated while
the heat in ON*
1
Operated depends on
the condition*
2
7
Airflow set in case of
heat thermo-OFF
Low*
3
Extra low*
3
8
Setting airflow*
3
Depends on SW1-7
9
Auto restart function
Effective
Not effective
0
Power ON/OFF by breaker
Effective
Not effective
SW2
Capacity
code
setting
1–6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
P12
Capacity
SW2
SW2
P15
P18
P24
P30
P36
ON
OFF
1 2 3 4 5 6
P08
ON
OFF
1 2 3 4 5 6
P48
Capacity
Before
power
supply
ON
Indoor controller board
<Initial setting>
Set for each capacity.
SW3
Function
setting
1
Heat pump/Cooling only Cooling only
Heat pump
Under
suspension
Indoor controller board
<Initial setting>
Set for each capacity.
ON
OFF
1 2 3 4 5 6 7 8 9 0
*
4
Refer to the <Table C> below for
SW3-5 and SW-3-6.
2
Louver/Humidifier
—
—
3
Unused
—
Before power
supply ON
4
5
Vane horizontal angle
1
Second setting*
4
First setting*
4
Under
suspension
6
Vane horizontal angle
2
Third setting*
4
Depends on SW3-5
7
Changing the opening of
linear expansion valve Effective
Not effective
8
Sensible temperature correction
Not effective
Effective
9
Unused
—
0
SW4
Model selection
1–6
Before
power
supply
ON
Indoor controller board
Service controller board only
<Table A>
SW1-7
SW1-8
OFF
OFF
Extra low
ON
OFF
Low
OFF
ON
Setting airflow
ON
ON
stop
Continue to the next page
1 2 3 4 5 6
ON
OFF
<Table C>
SW3-5
SW3-6 Vane setting Initial setting Setting
Vane position
OFF
OFF
Setting
1
●
Standard
Standard
ON
OFF
Setting
2
Less draft*
5
Upward position than the standard
OFF
ON
Setting
3
Less smudging Downward position than the standard
ON
ON
Unused
─
─
*
5
Be careful of the smudge on ceiling.
OCH611D