45
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
10. Removing the drain pump (DP) and float switch (FS)
(1) Remove the drain pan. (See Photo 6)
(2) Cut the hose band and remove the hose.
(3) Remove the drain pump assembly (3 screws and 2 hooks).
(4) Remove the drain pump (3 screws).
(5) Remove the float switch (2 screws).
Photo 7
Photo 8
Drain pump
Hose band
Float switch
Drain pump
assembly fixing screw
Drain pump fixing screw
Float switch fixing screw
11. Removing the heat exchanger
(1) Remove the drain pan. (See Photo 6)
(2) Remove the 3 screws of the piping cover, and pull out
piping cover.
(3) Remove the 2 screws of coil plate.
(4) Remove the 2 screws of the coil.
(5) Remove the screw of the coil support.
(6) Pull out the heat exchanger.
Photo 9
Coil support fixing screw
Heat exchanger
fixing screw
Coil support
Heat exchanger
Coil plate
Piping cover
OCH529