31
9-7. TEST POINT DIAGRAM
Indoor controller board
PLA-ZRP100BA
CN90
Connect to the wireless
remote controller board (CNB)
CN20
Room temperature
thermistor (TH1)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
CNP
Drain-pump output (DP)
(220-240V AC)
CNAC
Connect to the auto grille
controller board (CN3A)
(220-240V AC)
CNMF
Fan motor
1
-
4
: DC 310~340V
5
-
4
: DC15V
CN44
Pipe temperature
thermistor
1
-
2
: Liquid (TH2)
3
-
4
: Condenser/Evaporator(TH5)
CN4F
Drain float switch (FS)
CN4Y
i-see sensor
CN6Y
i-see sensor motor output
12V DC pulse output
CN105
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector
(HA terminal-A)
CN22
Connect to the terminal
block (TB5)
(Remote controller con-
necting wire)
(10.4~14.6V DC)
LED3
Transmission (Indoor/outdoor)
CN01
Connect to the Terminal Block (TB4)
(Indoor/outdoor connecting line)
Between
3
and
5
220-240V AC
CN3G
Connect to the auto grille controller board (CN3G)
13V pulse output
CNV
Vane motor output (MV)
12V pulse output
SWE
Emergency operation
Jumper wire J41,J42
Pair No. setting for wireless
remote controller
FUSE 6.3A /250V
V
CC
: Voltage between pins of
C955 15VDC
(Same as
5
(+)–
4
(-) of CNMF)
CN32
Connector
(Remote switch)
CN51
Centrally control
1
-
2
: Control signal
13V pulse input (
1
: +)
3
-
4
: Operation indicator
13VDC (
3
: +)
3
-
5
: Malfunction indicator
13VDC (
3
: +)
OCH529