6. Electrical work
Function table (Table 1)
Select unit number 00
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Power failure automatic recovery
Not available
01
1
Available *1
2
Ο *2
Indoor temperature detecting
Indoor unit operating average
02
1
Ο
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
Ο
Supported (indoor unit is not equipped with outdoor-air
intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
240 V
04
1
220 V, 230 V
2
Ο
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode no. Setting no. Initial setting
setting
Filter sign
100 Hr
07
1
2500 Hr
2
Ο
No filter sign indicator
3
Fan speed
Silent (low ceiling)
08
1
Standard
2
Ο
High ceiling
3
No. of air outlets
4 directions
09
1
Ο
3 directions
2
2 directions
3
Installed options (high efficiency filter)
Not supported
10
1
Ο
Supported
2
Up/down vane setting
Downward setting (vanes angle setup
3
)
11
1
Middle setting (vanes angle setup
1
)
2
Draft - less setting (vanes angle setup
2
)
3
Ο
3D i-see Sensor positioning
Position
1
12 *3
1
Position
2
2
Position
3
(Default)
3
Ο
3D i-see Sensor ceiling height setting
(when installing the 3D i-see Sensor panel)
Low ceiling (ceiling height: less than 2.7 m)
26
1
Standard (ceiling height: 2.7 – 3.5 m)
2
Ο
High ceiling (ceiling height: 3.5 – 4.5 m)
3
Fan speed during the cooling thermostat is OFF
Setting fan speed
27
1
Stop
2
Extra low
3
Ο
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
*3 When the 3D i-see Sensor corner panel position is changed, change this mode. Refer to page 19.