background image

12

6.3. Function settings 

6.3.1.  By wired remote controller

1

  (Fig. 6-11)

•  Select “Service” from the Main menu, and press the [SELECT] button.

•  Select “Function settings” with the [F1] or [F2] button, and press the [SELECT] 

button.

2

  (Fig. 6-12)

•  Set the indoor unit refrigerant addresses and unit numbers with the [F1] through 

[F4] buttons, and then press the [SELECT] button to confi rm the current setting.

<Checking the Indoor unit No.>

When the [SELECT] button is pressed, the target indoor unit will start fan operation. 

If the unit is common or when running all units, all indoor units for the selected 

refrigerant address will start fan operation.

3

  (Fig. 6-13)

•  When data collection from the indoor units is completed, the current settings 

appears highlighted. Non-highlighted items indicate that no function settings are 

made. Screen appearance varies depending on the “Unit No.” setting.

(Fig. 6-14)

•  Use the [F1] or [F2] button to move the cursor to select the mode number, and 

change the setting number with the [F3] or [F4] button.

(Fig. 6-15)

•  When the settings are completed, press the [SELECT] button to send the setting 

data from the remote controller to the indoor units.

•  When the transmission is successfully completed, the screen will return to the 

Function setting screen.

6.  Electrical work

F1

F2

F3

F4

Service menu

Cursor

Main menu:

Test run

Input maintenance info.

Function setting

Check

Self check

F1

F2

F3

F4

Function setting

Cursor

Address

Monitor:

Ref. address

Unit No.

Grp.

/1/2/3/4/All

Fig. 6-11

Fig. 6-12

F1

F2

F3

F4

Function setting

Cursor

Cursor

Request:

Ref. address

Mode 1

Mode 2

Mode 3

Mode 4

Grp.

F1

F2

F3

F4

Function setting

Cursor

Cursor

Request:

Ref. address

Mode 7

Mode 8

Mode 9

Mode 10

Unit # 1

Fig. 6-13

Fig. 6-14

F1

F2

F3

F4

Function setting

Ref. address

Sending data

Grp.

Fig. 6-15

Fig. 6-16

Fig. 6-18

Fig. 6-17

Fig. 6-19

6.3.2.  By wireless remote controller

1

  Going to the function select mode

  Press the 

 button between of 5 seconds.

  (Start this operation from the status of remote controller display turned off.) 

[CHECK] is lighted and "00" blinks. (Fig. 6-16)

  Press the   button to set the "50".

  Direct the wireless remote controller toward the receiver of the indoor unit and 

press the 

 button.

2

  Setting the unit number

  Press the   button to set unit number 

A

. (Fig. 6-17)

  Direct the wireless remote controller toward the receiver of the indoor unit and 

press the 

 button.

3

  Select a mode

  Press the   button to set Mode number 

B

. (Fig. 6-18)

  Direct the wireless remote controller toward the receiver of the indoor unit and 

press the 

 button.

  Current setting number: 

1=1 beep (1 second)

   

 

 

2=2 beep (1 second each)

   

 

 

3=3 beep (1 second each)

4

  Selecting the setting number

  Use the   button to change the Setting number 

C

. (Fig. 6-19)

  Direct the wireless remote controller toward the receiver of the indoor unit and 

press the 

 button.

5

  To select multiple functions continuously

  Repeat select 

3

 and 

4

 to change multiple function settings continuously.

6

  Complete function selection

  Direct the wireless remote controller toward the sensor of the indoor unit and 

press the 

 

 button.

Note: 

Make the above settings on Mr. Slim units as necessary.

•  Table 1 summarizes the setting options for each mode number. 

•  Be sure to write down the settings for all functions if any of the initial set-

tings has been changed after the completion of installation work.

A

B

C

RG79F156K01_EN.indd   12

12/13/2016   1:14:22 PM

Summary of Contents for PLA-ZM-EA Series

Page 1: ...rna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εξωτερικής μονάδας πριν από την εγκατάσταση της μονάδας κλιματιστικού MANUAL DE INSTALAÇÃO Para uma utilização ...

Page 2: ...ack of oxygen in the room may result Keep gas burning appliances electric heaters and other fire sources igni tion sources away from the location where installation repair and other air conditioner work will be performed If refrigerant comes into contact with a flame poisonous gases will be released Ventilate the room if refrigerant leaks during operation If refrigerant comes into contact with a f...

Page 3: ...n using a torque wrench If tightened too much the flare nut can break after an extended period If the unit is run for long hours when the air above the ceiling is at high tem perature high humidity dew point above 26 ºC dew condensation may be produced in the indoor unit or the ceiling materials When operating the units in this condition add insulation material 10 20 mm to the entire surface of th...

Page 4: ...0 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit E Grille B Bolt pitch F Ceiling C Ceiling opening G Multi functional casement option D Outer side of Grille H Entire periphery Note that the space between ceiling panel of the unit an...

Page 5: ...9 cm long if the beams are separated by as much as 180 cm The size of the suspension bolts should be ø10 3 8 The bolts do not come with the unit 2 Ferro concrete structures Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts 3 6 Unit suspension procedures Fig 3 6 Suspend the main unit as shown in the diagram Figures given in parent...

Page 6: ...seating surface before tightening flare nut Use 2 wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully After connecting the refrigerant piping to the indoor unit be sure to test the pipe connections for gas leakage with nitrogen gas Check that there is no refrigerant leakage from the refrigerant piping to the indoo...

Page 7: ...s applied to the drain socket that damages the hose or causes the hose to become detached water leakage may result 1 Correct piping G Make the piping size large for grouped pip ing 2 Wrong piping 3 Grouped piping H Downward slope 1 100 or more A Insulation 9 mm or more I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation B Downward slope 1 100 or more C Support metal J Up to 85 cm D O D ø...

Page 8: ...or electrical box cover E Screw F Slide direction of the electrical box cover G Entry for power cable and indoor outdoor unit connecting cable H Secure with the cable strap I Earth cable J Indoor outdoor unit connecting terminal K Electrical wiring service panel remote controller L Entry for wired remote controller M Wired remote controller terminal N Secure with the cable strap Caution Wiring for...

Page 9: ... used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 3 The figures are NOT always against the ground S3 terminal has 24 VDC against S...

Page 10: ...onnection of all active phase conductors of the supply 2 Max 120 m 3 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 4 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than poly...

Page 11: ...nit ºC ºF A Time display 12 hour format 24 hour format B AUTO mode Single set point Dual set point C Pair No 0 3 D Backlight On Off E 4 1 Switching to the initial setting mode 1 Press the button 1 to stop the air conditioner 2 Press the button 2 The Function setting screen will be displayed and the function No A will blink Fig 6 9 Press the button 4 to change the function No 3 Check that function ...

Page 12: ...de 1 Mode 2 Mode 3 Mode 4 Grp F1 F2 F3 F4 Function setting Cursor Cursor Request Ref address Mode 7 Mode 8 Mode 9 Mode10 Unit 1 Fig 6 13 Fig 6 14 F1 F2 F3 F4 Function setting Ref address Sending data Grp Fig 6 15 Fig 6 16 Fig 6 18 Fig 6 17 Fig 6 19 6 3 2 By wireless remote controller 1 Going to the function select mode Press the button between of 5 seconds Start this operation from the status of r...

Page 13: ...lent low ceiling 08 1 Standard 2 Ο High ceiling 3 No of air outlets 4 directions 09 1 Ο 3 directions 2 2 directions 3 Installed options high efficiency filter Not supported 10 1 Ο Supported 2 Up down vane setting Downward setting vanes angle setup 3 11 1 Middle setting vanes angle setup 1 2 Draft less setting vanes angle setup 2 3 Ο 3D i see Sensor positioning Position 1 12 3 1 Position 2 2 Positi...

Page 14: ...r power is turned on PLEASE WAIT is displayed for 2 minutes during system startup Normal After power is turned on PLEASE WAIT is dis played for 3 minutes then error code is displayed After startup is displayed green once and red once blink alternately F1 Incorrect connection of outdoor terminal block R S T and S1 S2 S3 After startup is displayed green once and red twice blink alternately F3 F5 F9 ...

Page 15: ...door controller board LED 1 microcomputer power supply Indicates whether control power is supplied Make sure that this LED is always lit LED 2 remote controller power supply Indicates whether power is supplied to the wired remote controller The LED is lit only for the indoor unit that is connected to the outdoor unit that has an address of 0 LED 3 indoor outdoor unit communication Indicates whethe...

Page 16: ... For details check the LED display of the outdoor controller board 2 UP Compressor overcurrent interruption 3 U3 U4 Open short of outdoor unit thermistors 4 UF Compressor overcurrent interruption When compressor locked 5 U2 Abnormal high discharging temperature 49C worked insufficient refrigerant 6 U1 Ud Abnormal high pressure 63H worked Overheating protection operation 7 U5 Abnormal temperature o...

Page 17: ...tem start up Correct operation PLEASE WAIT Error code Subsequent to about 2 minutes after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not con nected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1...

Page 18: ...take grille from the grille as indicated by the arrows 2 9 2 2 Removing the corner panel Fig 9 4 Loose the 4 screws on the corner Slide the corner panel in the direction of the arrow 1 in the figure and remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille 1 C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 9 3 Selection of air outlets For...

Page 19: ...clamp into the electrical box 9 4 5 Installing signal receiver Fig 9 9 Route the lead wire white 9 poles for signal receiver corner panel from the side of the electrical box on the main unit Make sure to connect to CN90 white on the controller board Make sure that the lead wire of the signal receiver corner panel is passed through the claw of bellmouth The remaining lead wire must be held together...

Page 20: ...t be supported by some models F1 F2 F3 F4 Check menu Cursor Service menu Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code Smooth maintenance Begin Smooth maintenance Exit Ref address Stable mode Cursor Ref address Stable mode Stabilization Collecting Cool Heat Normal Address Cool Heat Normal Smooth maintenance Return Smooth maintenance Return Smooth mai...

Page 21: ...is manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79F156K01 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: