9
6. Electrical work
ON/OFF
TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESET
SET
CLOCK
MODEL SELECT
Fig. 6-7
)LJ
Fig. 6-9
6.2. Remote controller
When using a wired remote controller together with a wireless remote controller, use
the following IR wireless remote controller.
6.2.1. For wired remote controller
1) Two wired remote controllers setting
If two wired remote controllers are connected, set one to “Main” and the other to
“Sub”. For setting procedures, refer to “Function selection of remote controller” in the
operation manual for the indoor unit.
Note:
When connecting two wired remote controllers, be sure to use the same model
of remote controller.
6.2.2. For IR wireless remote controller
1) Setting (Fig. 6-7)
1
Insert batteries.
2
Press the SET button with something sharp at the end.
MODEL SELECT
blinks and Model No. is lit.
3
Press the temp
buttons to set the Model No.
,I\RXPLVWRRNWKHRSHUDWLRQSUHVVWKH212))
button and operate again
from procedure
2
.
4
Press the SET button with something sharp at the end.
MODEL SELECT
and Model No. are lit for three seconds, then turned off.
Indoor
Outdoor
A
Model No.
PLA
heat pump models
001
cooling only models
033
$XWRPDWLFIDQVSHHGVHWWLQJ)RU,5ZLUHOHVVUHPRWHFRQWUROOHU)LJ
It is necessary to set for IR wireless remote controller only when automatic fan
speed is not set at default setting.
It is not necessary to set for wired remote controller with automatic fan speed at
default setting.
1
Press the SET button with something sharp at the end.
Operate when display of remote controller is off.
MODEL SELECT
blinks and Model No. is lit
A
.
2
3UHVVWKH$8726723
button.
blinks and setting No. is lit
B
.
(Setting No.01: without automatic fan speed )
3
Press the temp.
buttons to set the setting No.02.
(Setting No.02: with automatic fan speed )
,I\RXPLVWRRNWKHRSHUDWLRQSUHVVWKH212))
button and operate again
from procedure
2
.
4
Press the SET button with something sharp at the end.
MODEL SELECT
and Model No. are lit for 3 seconds, then turned off.
$VVLJQLQJD,5ZLUHOHVVUHPRWHFRQWUROOHUWRHDFKXQLW)LJ
Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a IR wireless remote controller
is assigned to the same pair No.
,5ZLUHOHVVUHPRWHFRQWUROOHUSDLUQXPEHUVHWWLQJRSHUDWLRQ)LJ
1
Press the SET button with something sharp at the end.
Start this operation from the status of IR wireless remote controller display turned
off.
MODEL SELECT
blinks and Model No. is lit.
2
Press the
min
button twice continuously.
Pair No. “0” blinks.
3
Press the temp
buttons to set the pair number you want to set.
,I\RXPLVWRRNWKHRSHUDWLRQSUHVVWKH212))
button and operate again
from procedure 2.
4
Press the SET button with something sharp at the end.
Set pair number is lit for three seconds then turned off.
A
Pair No. of IR wireless remote controller
Indoor PC board
0
Factory setting
1
Cut J41
2
Cut J42
3-9
Cut J41, J42