33
OCH715
LED1
Main power supply
(Indoor unit : 208/230
V AC)
CN44
Pipe temperature thermistor
1
-
2
: Liquid (TH22)
3
-
4
: Gas (TH23)
CN60
Linear expansion valve(LEV)
12 VDC pulse output
SW3
Function setting
SW22
Pair No. setting for wireless
remote controller
CN105
IT Terminal
CN32
Remote switch
CNV
Vane motor (MV1,MV2)
12 VDC pulse output
CN51
Centrally control
1
-
2
: Control signal
12 V DC pulse input (
1
: +)
3
-
4
: Operation indicator
12 V DC (
3
: +)
3
-
5
: Malfunction indicator
12 V DC (
3
: +)
CN52
Remote indicator
1
-
2
: Status lamp 12 V DC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12 V DC (
1
: +)
1
-
4
: Heating status lamp
12 V DC (
1
: +)
LED2
Power supply for
MA-Remote controller
9-3. TEST POINT DIAGRAM
9-3-1. Indoor controller board
(I.B)
PKFY-P04NLMU-E.TH
PKFY-P06NLMU-E.TH
PKFY-P08NLMU-E.TH
PKFY-P12NLMU-E.TH
PKFY-P15NLMU-E.TH
PKFY-P18NLMU-E.TH
Note: The voltage range of 12 V DC in this page is between 11.5 to 13.7 V DC.
SW2
Capacity setting
CN2M
M-NET transmission connecting wire
24 − 30 VDC (non-polar)
CN4F
Drain float switch (FS) :
(OPTION)
CN2A
MA-Remote controller
connecting wire
1
-
2
: 8.7 − 13 VDC (non-polar)
CNRU
Connect to SWITCH BOARD
(S.B),LED BOARD (L.B)
and PCB FOR WIRELESS
REMOTE CONTRILLER (W.B)
CNP
Drain pump (DP) : (OPTION)
1
-
3
: 12 VDC
CND
Power supply for indoor
controller board
3
-
5
: 208/230V AC
F1
Fuse
T3.15AL250V
CNAD
Connect to ADDRESS BOARD (A.B)
SWE
Test run (Drain pump and
indoor
fan motor)
CN20
Room temperature
thermistor (TH21)
CNMF
Connect to the Fan motor (MF)
1
-
4
: 294/325 VDC
5
-
4
: 15 VDC
6
-
4
: 0 VDC (FAN stop)
1 − 6.5 VDC (FAN operation)
CN24
External heater