8
SPECIFICATIONS
3
3-1. SPECIFICATION
Input
Current
Type
✕
No.
Air flow High - Low
External static pressure
Fan motor output
Item
Power source
Cooling capacity
Heating capacity
Exterior <munsell symbol>
Dimensions
Heat exchanger
Fan
Insulator
Air filter
Pipe dimensions
Drain pipe dimension
Noise level High - Low
Product weight
Unit
[
,V,Hz
kW
kW
kW
kW
A
A
—
mm
mm
mm
—
—
k
/min
Pa
kW
—
—
[
mm(in.)
[
mm(in.)
[
mm
dB
kg
Cooling
Heating
Cooling
Heating
Height
Width
Depth
Gas side
Liquid side
7.1
8.0
340
1,400
235
20 - 15
0.04
15.88(5/8")
9.52(3/8")
45 - 39
24
PKFY-P63VFM-E
PKFY-P100VFM-E
0.14
0.14
0.64
0.64
0.12
0.12
0.55
0.55
11.2
12.5
340
1,680
235
28 - 22
0.07
15.88(5/8") : R410A / 19.05(3/4") : R407C/ R22
9.52(3/8")
46 - 41
28
Electric
characteristic
Single phase, 220-230-240V, 50Hz / 220V, 60Hz
Plastic , white : <3.4Y 7.7/0.8>
Cross fin(Aluminum plate fin and copper tube)
Line flow fan
✕
2
0
Polyethylene sheet
PP Honeycomb fabric
Drain socket (Accessory) O.D. 20 <PVC pipe VP-20 connectable>
Note : Rating conditions (JIS B8616)
Cooling : Indoor D.B. 27°C
W.B. 19.0°C
Outdoor D.B. 35°C
W.B. 24°C
Heating : Indoor
D.B. 20°C
Outdoor D.B. 7°C
W.B. 6°C