3-2. ELECTRICAL PARTS SPECIFICATIONS
Room temperature thermistor
Liquid pipe temperature thermistor
Gas pipe temperature thermistor
Fuse
(Indoor controller board)
Fan motor
(with inner-thermostat)
Fan motor capacitor
Vane motor
Linear expansion valve
Power supply terminal block
Transmission terminal block
MA remote controller
terminal block
Dew prevention heater
Symbol
TH21
TH22
TH23
FUSE
MF
C1
MV
LEV
TB2
TB5
TB15
H2
PKFY-P63VFM-E
Resistance 0
°
C/15k
Ω
, 10
°
C/9.6k
Ω
, 20
°
C/6.3k
Ω
, 25
°
C/5.2k
Ω
, 30
°
C/4.3k
Ω
, 40
°
C/3.0k
Ω
Resistance 0
°
C/15k
Ω
, 10
°
C/9.6k
Ω
, 20
°
C/6.3k
Ω
, 25
°
C/5.2k
Ω
, 30
°
C/4.3k
Ω
, 40
°
C/3.0k
Ω
Resistance 0
°
C/15k
Ω
, 10
°
C/9.6k
Ω
, 20
°
C/6.3k
Ω
, 25
°
C/5.2k
Ω
, 30
°
C/4.3k
Ω
, 40
°
C/3.0k
Ω
250V 6.3A
OFF 130
±
5
;
MP 35 EA DC12V
(L, N,
;
) 330V 30A
(M1, M2, S) 250V 20A
(1,2) 250V 10A
28.8W / 240V
Service Ref.
Parts name
PKFY-P100VFM-E
Inner-thermostat
DC12V Stepping motor drive
Port dimension
[
5.2 (0 ~ 2,000pulse)
DC12V Stepping motor drive
Port dimension
[
3.2 (0 ~ 2,000pulse)
D10A4P70MS
220-230-240V / 50Hz , 220V / 60Hz
4pole Output 70W
D094P40MS
220-230-240V / 50Hz, 220V / 60Hz
4pole Output 40W
2.0
=
440V
3.0
=
440V