26
OPERATING PROCEDURE
PHOTOS
Photo 10
Photo 9
Screw of the
damper motor
Lead wires of the damper motor
Photo 11
Screw of
the motor band
Screw of the
ground wire
Screw of the damper
motor support
6. Removing the damper motor and the damper
limit switch
(1) Remove the panel. (Refer to 1.)
(2) Remove the screws of the nozzle assembly (lower).
(See Photo 8.)
(3) Remove the drain hose from the nozzle assembly (lower)
and pull out the nozzle assembly (lower) toward you.
(4) Remove the tape fixing the lead wires of the damper motor
from the nozzle assembly <lower>. (See Photo 9.)
(5) Remove the screws of the damper motor support, and
then the damper motor support.
(6) Remove the screws of the damper motor, and then the
damper motor from the damper motor support.
(7) Disconnect the connector from the damper motor.
(8) Remove the damper limit switch. (LS).
7. Removing the indoor fan motor
(1) Remove the panel. (Refer to 1.)
(2) Remove the nozzle assembly (lower) and the drain hose.
(Refer to 6.)
(3) Remove the screw of the ground wire of the indoor fan
motor (lower), and then the ground wire. (See Photo 11.)
(4) Remove the screw of the motor band, and then the motor
band. (See Photo11.)
(5) Remove the line flow fan and the indoor fan motor (lower)
from the box.
Photo 8
Screw of
the nozzle
Screw of
the nozzle
Drain
hose
Summary of Contents for PFFY Series