Details of Maintenance/Inspection
41
· Check for unusual noise
· Measure the insulation
resistance
· Check for excessive slack
· Check for wear and tear
· Check for unusual noise
· Check for unusual noise
· Free of unusual noise
· Insulation resistance over 1M
Ω
· Resistance (3-4kg/belt)
· Adequate amount of slack=5mm
· Belt length=no longer than
102% of the original length
· Free of wear and tear
· Free of unusual noise
· Free of unusual noise
Replace when insulation
resistance is under 1M
Ω
· Check for clogging of the
drainage system
· Check for loosened bolts
· Check for corrosion
· Clean, free of clogging
· Free of loose screws
· No major disintegration
Clean if dirty or clogged
Tighten bolts
Replace if extremely worn
· Perform an operation check
using the operation data
· Adequately controls the air
temperature
(Check temperature change on
the centralized controller)
Replace if malfunctioning
· Check for torn wire, fraying,
and unplugged connectors
· Check insulation resistance
· No frayed or cut wires or
unplugged connectors
· Insulation resistance over 1M
Ω
Replace when cut or shorted,
when the insulation resistance
goes below 1M
Ω
, or if there is a
history of abnormal operation
· Check for unusual sound
· Measure insulation resistance
· Look for abnormal history
· Free of unusual sound
· Insulation resistance over 1M
Ω
· No heatsink overheat protection
(4230,4330) on the report
Replace when producing unusual
sounds, when insulation resistance
goes under 1M
Ω
, or if there is a
history of abnormal operation.
· Perform an operation check
using the operation data
· Adequately controls the air
temperature
(Check temperature change on
the centralized controller)
Replace if malfunctioning
· Check for clogging, dirt, and
damage
· Clean, free of clogging or
damage
Clean
· Check for unusual noise
· Measure insulation resistance
· Free of unusual sound
· Insulation resistance over 1M
Ω
Replace if insulation resistance
goes below 1M
Ω
· Make sure the lamp comes on
· Comes on when the output is
on
Replace if the light does not
come on when the power is on
· Check for clogging, dirt, and
damage
· Clean, free of clogging or
damage
Clean
· Check for clogging and tear
· Clean the filter
· Clean, free of damage
Clean the filter
Replace if extremely dirty or
damaged
· Check the outer appearance
· Make sure its free of foreign
objects
· Free of frayed or cut wires
· Free of foreign objects
Replace if damaged or
extremely worn
Remove foreign objects
· Make sure the loop of the hose
has water to prevent air from
traveling through the hose
(Fill the hose with water)
· Check for clogging of the
drainage system
· Clean, free of clogging
· Free of wear and tear
Clean if dirty or clogged
Replace if extremely worm
· Check for unusual noise
· Check insulation resistance
· Check for loosened terminals
· Free of unusual sound
· Insulation resistance over 1M
Ω
· Free of loosened terminals
Replace if insulation resistance
goes below 1M
Ω
(under the
condition that the refrigerant
is not liquefied)
Tighten loosened bolts
Adjust the belt
Replace if the belt length
exceeds 2% of the original
length, worn, or used over 8000
hours
If the noise doesn't stop after
lubrication, change the oil.
Add lubricant once a year.
Parts
Fan motor
Bearing
Fan belt
Air filter
Linear
expansion valve
Indicator lamp
Compressor
Fan motor
Linear
expansion valve
6
months
6
months
6
months
6
months
3
months
Check points
Inspection
Cycle
Unit
What to do
Assessment
Drain pan
Drain hose
Inverter cooling
fan
Float switch
Heat exchanger
Pressure switch
Heat exchanger
Indoor
Outdoor
1
year
1
year
1
year