Rating Conditions (ISO T1)
OUTDOOR UNIT
REFRIGERANT
PIPING
Service Ref.
Power supply
External finish
Heat exchanger
Fan
Operation control & Thermostat
Noise level(Lo-Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side
Outdoor side
Height difference
Piping length
Liquid
Gas
Cooling
W
D
H
Input
Running current
Starting current
Fan(drive)
)
No.
Fan motor output
Airflow(Lo-Hi)
External static pressure
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan(drive)
)
No.
Fan motor output
Airflow
Charge
Compressor oil (Model)
W
D
H
Item
Service Ref.
PCA-P5HA
Function
Total input
Upper limit
Lower limit
Indoor
D.B. 35
:
, D.B. 22.5
:
D.B. 19
:
, D.B. 15
:
Outdoor
D.B. 46
:
D.B. -5
:
Cooling
INDOOR UNIT
Cooling
44,400
13,000
4.90
PCA-P5HA
Single phase, 50Hz, 220-230-240V
0.26
1.19
2.38
Stainless steel
Plate fin coil
Sirocco (direct)
✕
4
0.08+0.08
30-38 <1,060-1,350>
0 (direct blow)
Remote controller & built-in
44-50
26(1)
1,520(59-7/8)
650(25-5/8)
280(11)
56(124)
PU-P5YGAA
1
.UK
3-phase, 50Hz, 380-400-415V (4wires)
6.85
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
ZR61KCW-TFD
3.5
Line start
Anti-phase protector, Internal thermostat, HP switch, Thermal relay, Discharge thermo
38
Plate fin coil
Propeller (direct)
✕
2
0.070+0.070
95(3,360)
—
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
112(247)
R407C
4.6(10.1)
1.690 (Ester) 3MAW-POE
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Btu/h
W
kW
kW
A
A
kW
K
/min <CFM>
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
KW
W
kW
K
/min <CFM>
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
2. Guaranteed operating range
Capacity
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27
:
(80°F), W.B. 19
:
(66°F)
Outdoor : D.B. 35
:
(95°F), W.B. 24
:
(75°F)
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz
OC289--1.qxp 03.3.19 10:50 AM Page 9