65
Function settings
2
The default setting is “Disabled.”
To limit the settable temperature ranges for the
Auto, Cool (Drying), and Heat modes, touch the
[Disabled]
button to change it to
[Enabled]
.
Set the upper and lower limit temperatures for
the following operation modes in the table below
with the
buttons. (The temperatures will
decrease or increase by 1ºF or 1ºC increments.)
•
If the connected indoor unit does not feature the AUTO
mode, the items related to the Auto mode will not be
displayed.
Settable upper and lower limit temperatures
Operation mode
Lower limit
Upper limit
Auto (Single)
67°F–83°F
(19°C–28°C)
83°F–67°F
(28°C–19°C)
Cool/Drying, Auto (Dual)_Cool
67°F–95°F
(19°C–35°C)
95°F–67°F
(35°C–19°C)
Heat, Auto (Dual)_Heat
40°F–83°F
(5°C–28°C)
83°F–40°F
(28°C–5°C)
* “Auto (single set point)” is referred to as “Auto (Single)” in the table.
“Auto (dual set points)” is referred to as “Auto (Dual)” in the table.
* The settable operation modes and temperature ranges
vary, depending on the indoor unit model.
* The cooling and heating temperature ranges can be set
under the following conditions.
- The difference between the cooling and heating
upper limit temperatures is equal or greater than the
minimum temperature difference that varies with the
indoor unit model.
- Thee difference between the cooling and heating
lower limit temperatures is equal or greater than the
minimum temperature difference that varies with the
indoor unit model.
* The settable temperature range for the Setback mode
cannot be limited.