4
GB
2 Product Feature
2-1. Specification
2-2. Power supply coefficient, power consumption coefficient, and L coefficient
2-3. Appearance
CAUTION
Source power requirement
Rated input
voltage and current
EU: ~220 V - 240 V ; 0.7 A / 50 Hz Single-phase
US: ~208 V - 230 V ; 0.7 A / 60 Hz Single-phase
Fuse: 2.0 A Time-delay type (IEC127-2 S.S.5)
Voltage/current of output on the
Transmission Booster side
DC28 V - 30 V 1.7 A (Maximum loading)
Environmental condition
Temperature
Operating range 0 - 40 °C / 32 - 104 °F
Storage range
-20 - 60 °C / -4 - 140 °F
Humidity
30 - 90 %RH (No condensation)
Dimensions
340 (H) × 360 (W) × 59.2 (D) mm / 13 7/16 (H) × 14 3/16 (W) × 2 3/8 (D) in
Weight
3.4 kg / 7 1/2 lb
Installation Environment
In the metal control panel box (indoor)
* This unit is installed and used in a business office or equivalent environment.
Sound Pressure Level
The A-weighted sound pressure level is below 70 dB.
Power supply
coefficient
Power consumption
coefficient
L coefficient
TB2
0
0
0
TB3
25
0
0
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
This appliance is intended to be used by expert or trained
users in shops, in light industry and on farms, or for
commercial use by lay persons.
360 (14 3/16)
340 (13 7/16)
240 (9 1/2)
325 (12 13/16)
UP
300 (1
1 7/8)
Cable fixture
TB1
Power line terminal
TB3
M-NET Transmission
terminal block 2
TB2
M-NET Transmission
terminal block 1
Cable fixture
Unit: mm (in)
59.2 (2 3/8)