OPERATING PROCEDURE
PHOTOS/FIGURES
5.
Removing the LEV assy
(1) Remove the controller cover. (See Photo 1)
(2) Remove the under panel. (See Photo 1)
(3) Remove 8 the insulations, then remove 9 pipe cover fix
-
ing screws (4 x 10). (See Photo 2-1)
(4) Loosen the side clamps, then disconnect the LEV con
-
nectors on the controller board.
(5) Remove the earth lead wires from the LEV assy.
(6) Pull out the lead wires through the hole to the controller
board side.
<Removing the header assy>
(6) Cut the band which fixes the header assy and LEV assy
together, then remove the rubber mount. (See Photo 3)
(7) Remove the header assy. (See Photo 5-1)
<Disassembling the pipe box>
(8) Remove 2 side panel fixing screws (4 x 10).
(See Photo 5-1)
(9) Pull out the pipe box (top) and separate it from the side
panel. (See Photo 5-2)
(10) Turn the pipe box (top) upside down. (See Photo 5-3).
(11)
Remove 5 insulations, then remove 5 pipe box (top)
fixing screws (4 x 10).
(12) Turn the pipe box (top) upside down again, facing the
pipe side up.
(13)
Separate the pipe box (center) from the pipe box (top).
(See Photo 5-4.)
(14)
Remove the LEV assy.
<Pipe box cap only for PAC-MK34BC>
The pipe box caps are placed in 2 unused pipe holes
between the pipe box top, center and under.
(See Photo 5-5)
Photo 5-1
Photo 5-2
Photo 5-4
Photo 5-3
Photo 5-5
Pipe box (center)
Insulations (15 x 15 x 35)
Pipe box
(top)
Pipe box caps
Pipe box (top) fixing screws
Side panel
Side panel fixing screws
LEV assy
Pipe box (top)
Earth lead wire
26