Items
Outdoor unit
PUHY-P500
Ambient temp.
Indoor
DB/WB
Outdoor
Quantity
Set
Indoor unit
Quantity in operation
Condition
Model
–
Main pipe
Piping
Branch pipe
m
Total piping length
Indoor unit fan notch
–
Refrigerant volume
kg
Outdoor
Total current
A
unit
Volts
V
LEV
Indoor unit
Pulse
opening
SC (LEV1)
Pressure
High pressure(after O/S)
/Low pressure(before accumulator)
MPa
Discharge (TH11/TH12)
Heat exchanger outlet (TH5)
Accumulator
Inlet
Outdoor
Outlet
Sectional
unit
Suction (Compressor)
˚C
temp.
Shell bottom (Compressor)
Indoor
LEV inlet
unit
Heat exchanger outlet
20.0/-
7.0/6.0
4
4
250
125
100
32
5
10
45
Hi
22.1
Compressor frequency (No.1/No.2)
Hz
26.8/24.5
380/415
400
406
332
254
-
2.89/0.68
76/81
4
1
1
1/1
24/27
39
72
PUHY-P550
20.0/-
7.0/6.0
4
4
250
140
125
50
5
10
45
Hi
28.1
27.6/25.3
380/415
400
384
406
373
-
2.83/0.69
76/79
4
1
1
1/1
26/29
38
72
50Hz : 102/50
60Hz : 84/60
50Hz : 99/50
60Hz : 93/60
- 93 -