2. Header branching system
Note: The branch piping can not be branched again after header branching.
Outdoor unit
First branch
Cap
Item
Piping section
Allowable value
Total piping length
A + a + b + c + d + e + f
Less than 300m
Length
Farthest piping length (L)
A + f
Less than 150m
Farthest piping length after first branch ( )
f
Less than 40m
Height
Upper outdoor unit
H
H
Less than 50m
Indoor – Outdoor
Lower outdoor unit
Less than 40m
difference
Indoor – Indoor
h
Less than 15m
3. Mixed line and header branching system
Note: The total model names downstream in the table below
represent that viewed from A-point in the above figure.
Note: The branch piping can not be branched
again after header branching.
Outdoor unit
First branch
(Branch joint)
Branch joint
Indoor
Branch header
Cap
To downstream unit
Item
Piping section
Allowable value
Total piping length
A + B + C + a + b + c + d + e
Less than 300m
Length
Farthest piping length (L)
A + B + b
Less than 150m
Farthest piping length after first branch ( )
B + b
Less than 40m
Upper outdoor unit
Less than 50m
Height
Indoor – Outdoor
Lower outdoor unit
Less than 40m
difference
Indoor – Indoor
h
Less than 15m
Indoor
Indoor
Indoor
Indoor Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
H’
H’