225
CHAPTER 8 FUNCTIONS
8
8.
4 CC-Link I
E
F
ield
N
e
tw
ork
F
unct
ion
8.4.2
Error notification function
When an error, warning, or alarm occurs, the temperature control module notifies the master station of it using remote
input signals and remote registers.
Remark
The notification of the error, warning, or alarm can be checked on the LED on the front of the module.
For details, refer to the following.
• PART NAMES (
(1) Notification of an error
The temperature control module notifies the master station of an error in the following method.
(a) Method for clearing an error
The method for clearing an error depends on the error type.
For details, refer to the following.
Lists of Error Codes (
(2) Notification of a warning or alarm
The temperature control module notifies that a warning or alarm occurs to the master station in the following
method.
Item
Description
Reference
Error flag (RXA)
Turns on when a moderate error or major error occurs.
Latest error code (RWr0)
An error code is stored when a moderate error or major error (except
hardware failures) occurs.
Error occurrence address (RWr1)
The address of remote buffer memory area where an error has
occurred is stored.
Item
Description
Reference
Warning flag (RX7)
Turns on when a minor error occurs.
Latest warning code (RWr2)
The error code or alarm code is stored when a minor error occurs.
Common