(2) Initial data setting completed flag (RX9)
After writing parameter data to the remote buffer memory using the REMTO instruction, turn on Initial data setting
request flag (RY9).
This signal turns on when the operating condition is changed.
When the values of remote buffer memory areas are changed, the signal is used as an interlock condition to turn
on and off Initial data setting request flag (RY9). For the remote buffer memory areas where the changed values
are enabled by turning on and off Initial data setting request flag (RY9), refer to the following.
• Lists of Remote Buffer Memory Areas (
(3) Error flag (RXA)
This signal turns on when a moderate or major error occurs.
The signal turns off when the error cause is eliminated. For the action for the error, refer to the following.
• Lists of Error Codes (
Common
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Initial data setting completed
flag (RX9)
(Setting value A)
(Setting value B)
Module power supply
*1
The operation is started
with the setting value A.
Parameter settings are
read from the non-volatile
memory.
The setting value is
changed by a user.
*1 When data link is started at the turning on of the module power supply
Initial data setting request
flag (RY9)
Remote READY (RXB)
*2
Parameter area
*2 After turning on and off Initial data setting request flag (RY9), check that Remote READY (RXB) has turned on and start the control.
The operation is started
with the setting value B.
Controlled by the temperature control module
Controlled by the program
Common