HOLD/CLEAR function
Whether to continue or stop the control when a stop error of the CPU module occurs or the communication is
disconnected can be selected using this function.
The following table shows the correspondence between the setting of "CH
_HOLD_CLEAR setting" and the
operation of the temperature control module in cases when an error of the module occurs, when an error of the CPU
module occurs/the operating status of the CPU module is STOP, and when the communication is disconnected.
*1
CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H) (
*2
CH
Operation monitor (RX11 to RX14) turns off.
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
_HOLD_CLEAR setting".
Status
Processing
Reference
"CH
_HOLD_CLEAR setting"
CLEAR
HOLD
Error
Temperature control
module write data error
Follow the operation of when an error occurs
Temperature control
module hardware error
Depends on the symptom of the hardware
CPU stop error
Stops the operation and turns off external
output
Continues the operation and performs
external output
CPU operation
RUN
STOP
Follows the stop mode setting
Continues the operation and performs
external output
Communication disconnection
Stops the operation and turns off external
output
Continues the operation and performs
external output
Important
By the failure of an output element or internal circuit, an abnormal output may occur. Construct a circuit to monitor output signals that could cause a serious
accident.
Standard
Heating-cooling