 WARNING:

When installing or moving the unit, do not mix anything other than specified refrigerant (R410A) into
the refrigerating cycle.
If air is mixed, it may cause the refrigerating cycle to get abnormally high temperature, causing a risk of
burst.

Tightening torque

N·m

kgf·cm

Cap for service port

13.7 to 17.7

140 to 180

Cap for stop valve

19.6 to 29.4

200 to 300

5-5

EARTHING WORK

Put the earth circuit to the ground in accordance with “Technical Standards for Electrical Installation”.

 CAUTION:

Do not connect the earth cable to any gas pipe, water pipe, lightening rod or telephone earth cable.
If there is some deficiency in earthing work, it may cause a risk of electric shock.

The product incorporates a frequency inverter and so requires earthing in order to observe electric charge and
noise caused by static electricity.

5-6

CHECKING AFTER INSTALLATION

After finishing the installation, check the following items again by marking  .

Have special circuits been provided?
Is power supply voltage as specified?
Has indoor/outdoor connecting wire been inserted into terminal block?
Has indoor/outdoor connecting wire been secured firmly?
Has intermediary connection between power cable and indoor/outdoor connecting wire been carried out?
Is combination of connection pipes and indoor/outdoor connecting wire correct (Room A, Room B, Room C,
Room D)?
Is earth cable connection correct?
Has leak test been carried out?
Has air purge been carried out?
Is stop valve fully open?
Has drain discharge been checked?
Is insulation over connection pipe joints correct?
Is strength of installation location well enough?
Have all of 

 WARNING and 

 CAUTION items in “1. THE FOLLOWING SHOULD ALWAYS BE OB-

SERVED FOR SAFETY” been checked?

5-7

GAS CHARGE

Perform gas charge to unit.

1

Connect gas cylinder to the service port of stop valve.

2

Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3

Replenish specified amount of the refrigerant, while operating the air conditioner for cooling.

Note:
In case of adding refrigerant, comply with the quantity specified for the refrigerating cycle.

 CAUTION:

For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is
charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and
the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be
impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked.
Thus, charge the refrigerant slowly.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 40°C) during
cold season. But never use naked fire or steam.

Indoor

unit

Union

Stop valve

Outdoor

unit

Union

Gauge manifold
valve (for R410A)

Charge hose (for R410A)

Refrigerant gas
cylinder
operating valve
(for R410A)

Refrigerant gas cylinder
for R410A with siphon

Refrigerant (liquid)

Electronic scale for
refrigerant charging

Liquid pipe

Gas pipe

Union

Stop valve with

service port

Union

5-8

TEST RUN

• Be sure to perform the test run for each unit. Make sure each indoor unit operates properly following the

installation manual attached to the unit.

• If you perform the test run for all indoor units at once, you cannot detect any erroneous connection, if any, of

the refrigerant pipes and the indoor/outdoor unit connecting wires.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3
minutes to protect the air conditioner.

5-9

EXPLANATION TO THE CUSTOMER

• Recommend the customer to read the OPERATING INSTRUCTIONS carefully.
• Using the OPERATING INSTRUCTIONS for each unit, explain the following to the customer, how to control

temperature, how to remove the air filters, how to remove or put the remote controller in the remote controller
holder, how to clean, precautions for operation, etc.

If the customer (user) is absent, explain to the purchaser (owner, building’s controller, etc) about those
points.

(MXZ-A32WV)

Summary of Contents for MXZ-A26

Page 1: ...LATION DIAGRAM ACCESSORIES 2 3 SELECTING THE INSTALLATION LOCATION 3 4 OUTDOOR UNIT INSTALLATION 4 5 INDOOR OUTDOOR UNITS CONNECTION FINISHING AND TEST RUN 6 HFC utilized R410A IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS 3000 S A A WIRING RULES THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR ...

Page 2: ...ing works It could cause an electric shock The appliance shall be installed in accordance with national wiring regulations When installing or relocating the unit make sure that no substance other than the speci fied refrigerant R410A enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion More than 100 mm Open as a rule More th...

Page 3: ...alling in a place with less strength may result in a unit falling causing a risk of injury CAUTION Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wire less equipment on onne...

Page 4: ...ocket to the hole 2Please close the rest of the holes with the drain caps 3Please connect a vinyl hose of 25 mm in the inside diameter on the market with the drain socket and lead drain 4 3 HOW TO REMOVE THE SERVICE PANEL AND THE CONNECT COVER Remove the four service panel securing screws and pull the panel down in an arrow direction to remove the service panel Remove the four connect cover securi...

Page 5: ... and Outdoor connecting wire Specification Cable 2 core 1 0 1 5 mm2 in conformity with Design 245 IEC 57 This installation manual is only for the outdoor unit installation In installing the indoor units refer to the installation manual attached to each indoor unit WARNING Use the indoor outdoor unit connecting wire that meets the Standards to connect the indoor and out door units and fix the wire ...

Page 6: ... connecting the model 12 13 or 18 to either unit A or B for MXZ A32WV and B or C for MXZ A26WV use optional different diameter joints MAC A454JP because the valve size of gas pipes for the outdoor unit is ø9 52 mm No need to use different diameter joints if the diameter of the pipe is ø9 52 mm When connecting the model 07 or 09 to either unit A or B for MXZ A32WV and A for MXZ A26WV use optional d...

Page 7: ...top valve on the gas pipe side of the outdoor unit The stop valve will not work in it initial state fresh out of the factory totally closed with cap on Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit Run the vacuum pump Vacuumize for more than 15 minutes Check the vacuum with the gauge manifold valve then close the...

Page 8: ... of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam Indoor unit Union Stop valve Outdoor unit Union Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder operating valve for R410A Refrigerant gas cylinder for R410A with siphon Refrigerant liquid Electronic scale for refrigerant charging Liquid pipe Gas p...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y347H01 ...

Reviews: