5-2

FLARING WORK

• Main cause of gas leakage is defect in flaring work.

Perform flaring work correctly in the following proce-
dure.

1. Pipe cutting

• Cut the copper pipe correctly with pipe cutter.

2. Burrs removal

• Completely remove all burrs from the cut cross

section of the pipe.

• Put the end of the copper pipe downward to pre-

vent burrs from dropping in the pipe.

3. Putting nut on

• Remove flare nuts attached to indoor and outdoor

units, then put them on pipe having completed
burr removal.
(not possible to put them on after flaring work)

5. INDOOR/OUTDOOR UNITS CONNECTION FINISHING AND

TEST RUN

Model

Pipe size for indoor unit

Allowable

name

connection pipe size

07

Liquid pipe

ø6.35 mm

ø6.35 mm

09

Gas pipe

ø9.52 mm

ø9.52 mm

12

Liquid pipe

ø6.35 mm

ø6.35 mm

13

Gas pipe

ø9.52/ø12.7 mm

ø9.52/ø12.7 mm

18

Liquid pipe

ø6.35 mm

ø6.35 mm

Gas pipe

ø12.7 mm

ø12.7 mm

24

Liquid pipe

ø6.35 mm

ø6.35 mm

Gas pipe

ø15.88 mm

ø15.88 mm

26

Liquid pipe

ø9.52 mm

ø9.52 mm

Gas pipe

ø15.88 mm

ø15.88 mm

Valve size for outdoor unit

Å

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø12.7 mm

ı

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø12.7 mm

Ç

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø9.52 mm

Î

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø9.52 mm

Indoor unit

Î

 UNIT

Indoor unit

Ç

 UNIT

Outdoor
unit

Indoor unit

ı

 UNIT

Indoor unit

Å

 UNIT

5-1

FLARED CONNECTIONS

PIPE LENGTH AND HEIGHT DIFFERENCE

Limits

A26WV

A32WV

Pipe length per indoor unit

25 m

max.

25 m

max.

Total pipe length for multi-system

50 m

max.

70 m

max.

Height difference

10 m

max.

10 m

max.

No. of bends per indoor unit

25

max.

25

max.

Total No. of bends for multi-system

50

max.

70

max.

Refrigerant adjustment ....... If pipe length exceeds 40 m, additional refrigerant (R410A) charge is required.
(The outdoor unit is charged with refrigerant for total pipe length up to 40 m.)

Pipe length

Up to 40 m

No additional charge is required.

Exceeding 40 m

Additional charge is required.
(Refer to the table below.)

Refrigerant to be added

20 g/m 

×

 (refrigerant piping length(m)-40)

• For pipe size, see the table below.

SELECTING PIPE SIZE

The diameter of connection pipes differs according to the type and capacity of indoor units. Match the diameters
of connection pipes for indoor and outdoor units according to the following table.

*

Connections at outdoor unit are described as unit A, B, C and D below corresponding to the indica-
tion on each valve.

• If the diameter of connection pipes does not match the diameter of pipe end connections, use optional

different-diameter joints.

• When connecting the model 12, 13 or 18 to either unit A or B for MXZ-A32WV and B or C for MXZ-A26WV,

use optional different-diameter joints MAC-A454JP because the valve size of gas pipes for the outdoor unit
is ø9.52 mm. (No need to use different-diameter joints if the diameter of the pipe is ø9.52 mm.)

• When connecting the model 07 or 09 to either unit A or B for MXZ-A32WV and A for MXZ-A26WV, use

optional different-diameter joints MAC-A455JP because the valve size of gas pipes for the outdoor unit is
ø12.7 mm.

• When connecting the model 24 to either unit A or B for MXZ-A32WV and A for MXZ-A26WV, use optional

different-diameter joints MAC-A456JP because the valve size of gas pipes for the outdoor unit isø 12.7 mm.

Connect the model 26 to unit A only.

Use optional different-diameter joints MAC-A456JP because the valve size of gas pipes for the outdoor unit
isø 12.7 mm and PAC-493PI because the valve size of liquid pipe is ø6.35 mm.

PIPING PREPARATION

1

If you use commercially available copper pipes, use the following table for pipe specifications.

Outside diameter

Wall thickness

Liquid pipe

ø6.35 mm

0.8 mm

Gas pipe

ø9.52 mm

0.8 mm

Gas pipe

ø12.7 mm

1.0 mm

Gas pipe

ø15.88 mm

1.0 mm

2

For insulation material, use 8 mm-thick heat-insulating expended polyethylene with a specific grarity of 0.045.

3

Ensure that the 2 refrigerant pipes are insulated to prevent condensation.

4

Refrigerant pipe bending radius must be 100 mm or more.

 CAUTION:

Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installa-
tion of the indoor unit and lack of thickness may cause dew drippage.

90

°

(MXZ-A32WV)

MXZ-A26WV

MXZ-A32WV

Valve size for outdoor unit

Å

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø12.7 mm

ı

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø9.52 mm

Ç

 UNIT

Liquid pipe

ø6.35 mm

Gas pipe

ø9.52 mm

Summary of Contents for MXZ-A26

Page 1: ...LATION DIAGRAM ACCESSORIES 2 3 SELECTING THE INSTALLATION LOCATION 3 4 OUTDOOR UNIT INSTALLATION 4 5 INDOOR OUTDOOR UNITS CONNECTION FINISHING AND TEST RUN 6 HFC utilized R410A IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS 3000 S A A WIRING RULES THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR ...

Page 2: ...ing works It could cause an electric shock The appliance shall be installed in accordance with national wiring regulations When installing or relocating the unit make sure that no substance other than the speci fied refrigerant R410A enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion More than 100 mm Open as a rule More th...

Page 3: ...alling in a place with less strength may result in a unit falling causing a risk of injury CAUTION Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wire less equipment on onne...

Page 4: ...ocket to the hole 2Please close the rest of the holes with the drain caps 3Please connect a vinyl hose of 25 mm in the inside diameter on the market with the drain socket and lead drain 4 3 HOW TO REMOVE THE SERVICE PANEL AND THE CONNECT COVER Remove the four service panel securing screws and pull the panel down in an arrow direction to remove the service panel Remove the four connect cover securi...

Page 5: ... and Outdoor connecting wire Specification Cable 2 core 1 0 1 5 mm2 in conformity with Design 245 IEC 57 This installation manual is only for the outdoor unit installation In installing the indoor units refer to the installation manual attached to each indoor unit WARNING Use the indoor outdoor unit connecting wire that meets the Standards to connect the indoor and out door units and fix the wire ...

Page 6: ... connecting the model 12 13 or 18 to either unit A or B for MXZ A32WV and B or C for MXZ A26WV use optional different diameter joints MAC A454JP because the valve size of gas pipes for the outdoor unit is ø9 52 mm No need to use different diameter joints if the diameter of the pipe is ø9 52 mm When connecting the model 07 or 09 to either unit A or B for MXZ A32WV and A for MXZ A26WV use optional d...

Page 7: ...top valve on the gas pipe side of the outdoor unit The stop valve will not work in it initial state fresh out of the factory totally closed with cap on Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit Run the vacuum pump Vacuumize for more than 15 minutes Check the vacuum with the gauge manifold valve then close the...

Page 8: ... of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam Indoor unit Union Stop valve Outdoor unit Union Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder operating valve for R410A Refrigerant gas cylinder for R410A with siphon Refrigerant liquid Electronic scale for refrigerant charging Liquid pipe Gas p...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y347H01 ...

Reviews: