9
4
SPECIFICATIONS
• Outdoor unit : MXZ-8B48NA/MXZ-8B48NAR1
Conversion formula:
kcal/h = kW
%
860
Btu/h =
kW
%
3412
CFM =
m
3
/min
%
35.31
Service Ref.
MXZ-8B48NA, MXZ-8B48NAR1
Standard performance
Indoor type
Non-Ducted
Mix
Ducted
Cooling
Capacity Rated / Max (*1)
Btu/h
48000 / 54000
Rated power consumption (*1)
W
5780
6125
6470
EER
Btu/Wh
8.30 7.84 7.42
SEER
Btu/Wh
15.0 14.8 14.7
Heating
Capacity Rated / Max 47 °F (*1)
Btu/Wh
54000 / 60000
Capacity 17 °F
*2
Btu/Wh
36600
36550
36500
Rated power consumption 47 °F (*1)
W
4820
5045
5270
COP 47 °F (*1)
Btu/Wh
11.20
10.70
10.25
HSPF
4
/
5
Btu/Wh
8.7 / 7.0
8.8 / 7.0
8.9 / 7.1
OUTDOOR UNIT
Connectable indoor units (Max.)
8
Max. Connectable Capacity
70200 Btu/Wh (130% of Outdoor Unit Max Capacity)
Power supply
208/230, 1, 60
Breaker Size / Max. fuse size
50A / 52A
Min. circuit ampacity
32A
Sound level (Cool/Heat)
dB
54 / 55
External
¿
nish
Munsell 3Y 7.8/1.1
Refrigerant control
Linear Expansion Valve
Compressor
Hermetic
Model
ANB33FDSMT
Motor output
kW
2.9
Starting method
Inverter
Heat exchanger
Plate
¿
n coil
Fan
Fan (drive) × No.
Propeller fan × 2
Fan motor output
kW
0.086 + 0.086
Air
À
ow
m³/min (CFM)
100 (3,530)
Dimensions
(H × W × D)
W
mm (in.)
980 (37-13/32)
D
mm (in.)
330+30 (13+1-3/16)
H
mm (in.)
1,350 (53-5/32)
Weight
kg (lbs)
126 (278)
Refrigerant
R410A
Charge
kg (lbs)
8.5 (18.7)
Oil / Model
L (oz)
2.3 (73) / FV50S
Protection devices
High pressure protection
HP switch
Compressor protection
Discharge thermo, Over current detection (MXZ-8B48NA)
Compressor thermo, Over current detection (MXZ-8B48NAR1)
Fan motor protection
Overheating / Voltage protection
Guaranteed operation range
(cool)
-5
〜
46 °C DB (23 ~ 115 °F DB)
(heat)
-15
〜
21 °C DB
(5 ~ 70 °F DB)
REFRIGERANT PIPING
Total Piping length (Max.)
m (ft)
115 (377)
Farthest
m (ft)
70 (300)
Max. Height difference
m (ft)
30 (98) (*3)
Chargeless length
m (ft)
40 (131)
Piping diameter
Liquid
[
mm (in.)
[
9.52 (3/8)
Gas
[
mm (in.)
[
15.88 (5/8)
Connection method
Indoor side
Flared
Outdoor side
Flared
(*1) Rating conditions
Cooling Indoor
: D.B.26.7°C / W.B.19.4°C (D.B.80°F / W.B.67 °F)
Outdoor : D.B.35.0°C (95°F)
Heating Indoor : D.B.21.1°C (70°F)
Outdoor : D.B.8.3°C / W.B.6.1°C (D.B.47°F / W.B.43°F)
(*2) Conditions
Heating Indoor : D.B.21.1°C (70°F)
Outdoor : D.B. - 8.3°C / W.B. - 9.4°C (D.B.17°F / W.B.15°F)
(*3) 20m (66ft)
:
In case of installing outdoor unit lower than indoor unit.
Note : Refer to the service manual of indoor unit for the indoor units speci
¿
cations.