72
<Branch box unit operation monitor function>
[When option part ‘A-Control Service Tool (PAC-SK52ST)’ is connected to branch box controller board (CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by
controlling DIP SW2 on ‘A-Control Service Tool’.
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Operation indicator SW2 : Indicator change of self diagnosis
<Digital indicator LED1 working details>
(Be sure that 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply is ON.
When the power supply is ON, blinking displays by turns.
Wait for 2 minutes at the longest.
(2) When the display lights (Normal operation)
1
The number of connected indoor units to this branch box (0 - 5)
1
ON
2 3 4 5 6
(Initial setting)
SW2
1 second
interval
LED1
(Lighting)
1
ON
2 3 4 5 6
Pipe temperature / Liquid (TH3)
– 40~90 (°C)
– 40~194 (°F)
w
– 40~90 (°C), – 40~194 (°F)
(When the coil thermistor detects 0
:
or below, “–”
and temperature are displayed by turns.)
(Example)
When –10
:
; 0.5 secs. 0.5secs. 2 secs.
°C
°F(
w
)
10
1
ON
2 3 4 5 6
Discharge/Compressor temperature
(TH4)
3~217 (°C)
37~327 (°F)
w
3~217 (°C), 37~327 (°F)
w
(When the discharge/compressor thermistor detects
100
:
or more, hundreds digit, tens digit and ones
digit are displayed by turns.)
(Example)
When 105
:
; 0.5 secs. 0.5secs. 2 secs.
°C
°F(
w
)
1
05
1
ON
2 3 4 5 6
Output step of outdoor FAN
0~15
Step
0~15
Unit number of this branch box
1~2
1 or 2
w
Omit the figures after the decimal fractions.
Code
display
1
ON
2 3 4 5 6
Compressor operating frequency
0~225
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example)
When 125Hz; 0.5 secs. 0.5secs. 2 secs.
Hz
1
25
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
LEV-A opening pulse
0~500
0~500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example)
When 150 pulse; 0.5 secs. 0.5secs. 2 secs.
Pulse
1
50
w
SW1-8 : OFF (Unit: °C), SW1-8 : ON (Unit: °F)