Mitsubishi Electric MXZ-6F120VGD Installation Manual Download Page 12

11

4-8. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to 

remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.
• 

To feel cool / warm wind, use lower fan speed or reduce the number of indoor units in operation.

  When many indoor units are being operated at the same time, capacity of each indoor unit may drop as shown in the graph below.

100%

150%

100%

67%

Ratio of total indoor units capacity to outdoor unit capacity

Capacity of each indoor unit

Operation when the total capacity of the operating indoor units is more than the capacity of the outdoor unit.

4-7. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires cannot be 

detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combination, 

and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not a mal

-

function.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the power 

supply.

•  Correction completes in 10 to 20 minutes. When the correction is completed, its result is 

shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch (SW871) 

again.

•  When the correction completed without error, do not press the piping/wiring correction switch 

(SW871) again.

When the result is “Not completed”, press the piping/wiring correction switch (SW871) again to 

cancel this function. Then, confirm the wiring and piping combination in a conventional manner 

by operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts other than 

the switch, including the P.C. board. This may cause electric shock or burn by hot parts and 

live parts around the switch. Contacting the live parts may cause P.C. board damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Lit

Lit

Once

Result of piping/wiring correction function

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Result

Lit

Not lit

Lit

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRECAU-
TIONS WHEN LED BLINKS” 
located behind the service 

panel.

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

3) Fully close the stop valve on the liquid pipe side of the outdoor unit.

4) Turn on the breaker.

5) Start the emergency COOL operation on all the indoor units.

6) When the pressure gauge shows 0 – 0.05 MPa [Gauge] (approx. 0 – 0.5 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and stop the 

operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  *  If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0 – 0.05 MPa [Gauge] (approx. 0 – 0.5 kgf/cm

2

), or the protec

-

tion function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect all of the 

refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 

WARNING

5.  PUMPING DOWN

VG79Y171H01_4th.indd   11

2020/04/21   10:59:57

Summary of Contents for MXZ-6F120VGD

Page 1: ... INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Split type Air Conditioner MXZ 6F120VGD VG79Y171H01_4th indd 1 2020 04 21 10 59 54 ...

Page 2: ...t circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety n Do not discharge the refrigerant into the atmospher...

Page 3: ... When installing the unit be sure to secure the unit legs Where it is at least 3 m away from the antenna of TV set or radio Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required for the affected device Install the unit horizontally Please install it in an area not affected by snowfall or blowing snow In areas with he...

Page 4: ...r more Blowing guide PAC SH96SG E Height of the obstacle is 1200 or less OK OK OK NG R32 is heavier than air as well as other refrigerants so tends to accumulate at the base in the vicinity of the floor If R32 accumulates around base it may reach a flammable concentration in case room is small To avoid ignition maintaining a safe work environment is required by ensuring appropriate ventilation If ...

Page 5: ...t C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 1...

Page 6: ...l There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 For wall mounted ceiling suspended cassette and concealed Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling suspended h0 2 2 m h0 2 2 m h0 2 2 m Only for MFXZ M kg...

Page 7: ... piping connection 3 Attach the drain socket to one of the several drain holes Fix the drain socket into the drain hole of the base using the catches to secure it in place 4 Connect the soft PVC hose I D 15 mm as shown in the illustration 5 Make sure to provide drain piping with a downhill grade for easy drain flow 6 Glue the drain caps to close all the other unnecessary holes with the glue Prepar...

Page 8: ...FOR OUTDOOR UNIT Terminal block for power supply Connecting order Connect the terminal block in following order A B C D E F P DR Terminal block for indoor outdoor unit Cable clamps 600 370 Service panel Screws Note Removing the handle increases the effectiveness of the wiring operation Be sure to reinstall the handle Terminal block for DRED Interface DRED Interface Power supply 35 mm 15 mm Lead wi...

Page 9: ... Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 C...

Page 10: ...ve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position 4 PURGING PROCEDURES LEAK TEST AND TEST RUN Stop valve cap Torque 24 4 to 30 4 N m 250 to 310 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Stop valve cap Torque 21 5 to 27 5 N m 220 to 280 kgf cm Mak...

Page 11: ...he setting referring to the table below 3 Turn on the main power for the air conditioner SW2 ON 1 2 3 4 5 6 20A ON 1 2 3 4 5 6 Factory setting Full SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 Lower the operating noise How to lower the operating noise 1 Be sure to turn off the main power for the air conditioner before making the setting 2 Set the 5 of SW1 on the outdoor controller boar...

Page 12: ...press the piping wiring correction switch SW871 again When the result is Not completed press the piping wiring correction switch SW871 again to cancel this function Then confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one The operation is done while the power is supplied Make sure not to contact parts other than the switch including the P C b...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...VG79Y171H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y171H01_4th indd 1 2020 04 21 10 59 57 ...

Reviews: