Mitsubishi Electric MXZ-6F120VGD Installation Manual Download Page 10

9

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. 

(The stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve 

on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge manifold 

valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge manifold 

valve remains in the same position. Confirm that pressure gauge shows -0.101 

MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating without 

fully opening lowers the performance and this causes trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be 

sure to charge slowly with liquid refrigerant. 

9) Tighten cap of service port to obtain the initial status.

10

) Leak test

Stop valve 

for GAS

Gauge mani-
fold valve (for 

R32, R410A)

Compound pressure 

gauge (for R32, R410A)

–0.101MPa 

 

(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump

(for R32, R410A)

Charge hose  

(for R32, R410A)

*Close

*Open

Hexagonal 
wrench

*4 to 5 turns

Stop valve 

 

for LIQUID

Pressure gauge

(for R32, R410A)

Precautions when us-
ing the control valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres

-

sure is applied. This may cause 

gas leak.

Service port

Charge hose 
(for R32, 

R410A)

Body

Close

Open

Control valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then  tighten  part A.  Do  not  tighten 

part A or turn the body when valve 

core is in open position.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Stop valve cap

(Torque 24.4 to 

30.4 N•m, 250 to 
310 kgf•cm

)

Service port cap

(Torque 10 to 12 N•m, 

100 to 120 kgf•cm

)

Service port cap

(Torque 10 to 12 N•m, 

100 to 120 kgf•cm

)

Stop valve cap

(Torque 21.5 to 

27.5 N•m, 220 

to 280 kgf•cm)

Make sure to replace the cap after 

the operation.

<R32>

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air condi

-

tioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrig

-

erating cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 

liquid refrigerant. Charge the liquid refrigerant slowly, otherwise the compressor 

will be locked.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant gas 
cylinder  

operating valve

(for R32, 

R410A)

Gauge manifold 
valve (for R32, 

R410A)

Charge hose 
(for R32, 

R410A)

Refrigerant gas cylinder for R32, R410A 

with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union

Union

 WARNING

When opening or closing the valve 
below freezing temperatures, 
refrigerant may spurt out from the 
gap between the valve stem and the 

valve body, resulting in injuries.

Cap

Valve stem

Valve body

 WARNING

To avoid risk of fire, make sure that there are no flammable hazards or 

ignition risks before opening the stop valves.

VG79Y171H01_4th.indd   9

2020/04/21   10:59:57

Summary of Contents for MXZ-6F120VGD

Page 1: ... INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Split type Air Conditioner MXZ 6F120VGD VG79Y171H01_4th indd 1 2020 04 21 10 59 54 ...

Page 2: ...t circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety n Do not discharge the refrigerant into the atmospher...

Page 3: ... When installing the unit be sure to secure the unit legs Where it is at least 3 m away from the antenna of TV set or radio Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required for the affected device Install the unit horizontally Please install it in an area not affected by snowfall or blowing snow In areas with he...

Page 4: ...r more Blowing guide PAC SH96SG E Height of the obstacle is 1200 or less OK OK OK NG R32 is heavier than air as well as other refrigerants so tends to accumulate at the base in the vicinity of the floor If R32 accumulates around base it may reach a flammable concentration in case room is small To avoid ignition maintaining a safe work environment is required by ensuring appropriate ventilation If ...

Page 5: ...t C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 1...

Page 6: ...l There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 For wall mounted ceiling suspended cassette and concealed Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling suspended h0 2 2 m h0 2 2 m h0 2 2 m Only for MFXZ M kg...

Page 7: ... piping connection 3 Attach the drain socket to one of the several drain holes Fix the drain socket into the drain hole of the base using the catches to secure it in place 4 Connect the soft PVC hose I D 15 mm as shown in the illustration 5 Make sure to provide drain piping with a downhill grade for easy drain flow 6 Glue the drain caps to close all the other unnecessary holes with the glue Prepar...

Page 8: ...FOR OUTDOOR UNIT Terminal block for power supply Connecting order Connect the terminal block in following order A B C D E F P DR Terminal block for indoor outdoor unit Cable clamps 600 370 Service panel Screws Note Removing the handle increases the effectiveness of the wiring operation Be sure to reinstall the handle Terminal block for DRED Interface DRED Interface Power supply 35 mm 15 mm Lead wi...

Page 9: ... Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 C...

Page 10: ...ve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position 4 PURGING PROCEDURES LEAK TEST AND TEST RUN Stop valve cap Torque 24 4 to 30 4 N m 250 to 310 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Stop valve cap Torque 21 5 to 27 5 N m 220 to 280 kgf cm Mak...

Page 11: ...he setting referring to the table below 3 Turn on the main power for the air conditioner SW2 ON 1 2 3 4 5 6 20A ON 1 2 3 4 5 6 Factory setting Full SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 Lower the operating noise How to lower the operating noise 1 Be sure to turn off the main power for the air conditioner before making the setting 2 Set the 5 of SW1 on the outdoor controller boar...

Page 12: ...press the piping wiring correction switch SW871 again When the result is Not completed press the piping wiring correction switch SW871 again to cancel this function Then confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one The operation is done while the power is supplied Make sure not to contact parts other than the switch including the P C b...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...VG79Y171H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y171H01_4th indd 1 2020 04 21 10 59 57 ...

Reviews: