background image

En-2

2. 

Front (blowing) side open

As long as space indicated 
in the figure is provided, it 
is allowed to install the unit 
where obstacles are behind 
and on the sides of the unit. 
(No obstacle above the unit)

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit → diameter of connection pipe)

MXZ-6C

Liquid / Gas

6.35 (1/4) → 9.52 (3/8) : PAC-493PI

9.52 (3/8) → 12.7 (1/2) : MAC-454JP

9.52 (3/8) → 15.88 (5/8) : PAC-SG76RJ

12.7 (1/2) → 9.52 (3/8) : MAC-A455JP

12.7 (1/2) → 15.88 (5/8) : MAC-A456JP

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A UNIT

6.35 (1/4) / 12.7 (1/2)

B - F UNIT

6.35 (1/4) / 9.52 (3/8)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.
•  Where airflow is good and dustless.
•  Where rain or direct sunshine can be avoided as much as possible.
•  Where neighbours are not annoyed by operation sound or hot air.
•  Where rigid wall or support is available to prevent the increase of op-

eration sound or vibration.

•  Where there is no risk of combustible gas leakage.
•  When installing the unit, be sure to secure the unit legs.
•  Where it is at least 3 m away from the antenna of TV set or radio. Op-

eration of the air conditioner may interfere with radio or TV reception in 
areas where reception is weak. An amplifier may be required for the af-
fected device.

•  Install the unit horizontally.
•  Please install it in an area not affected by snowfall or blowing snow. 

In areas with heavy snow, please install a canopy, a pedestal and/or 
some baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce 
vibration transmitted from there.

500 or more

200 or more

350 or more

100 or more

100 or more

500 or more

100 or more

Service space

350 or more 

350 or more

•  When installing the unit in an area that is enclosed with walls such 

as a verandah, be sure to have enough space as shown below. 

  In this case, the air conditioning capacity and power consumption 

might deteriorate.

•  When installing two or more units, do not install the units in front or 

behind each other.

200 or more

100 or more

350 or more

500 or more

500 or more

1. 

Obstacles above

When there is no obstacle in front 
and on the sides of the unit, it is al-
lowed to install the unit where an 
obstacle is above the unit only if the 
space shown in the figure is provided.

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of 
the unit as shown in the figure, open 
space above, behind, and on the 
sides of the unit is required.

5. 

Service space

Provide space for service and maintenance as shown in the figure.

500 or more

100 or more

(Unit: mm)

4. 

Obstacles in front, behind and on side(s)

Note: 

When operating the air conditioner in low outside temperature, be sure 
to follow the instructions described below.
•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

•  To prevent exposure to wind, it is recommended to install a baffle 

board on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 
is liable to occur.
•  Where flammable gas could leak.
•  Where there is much machine oil.
•  Salty places such as the seaside.
•  Where sulfide gas is generated such as a hot spring.
•  Where there is high-frequency or wireless equipment.
•  Where there is emission of high levels of VOCs, including phthalate 

compounds, formaldehyde, etc., which may cause chemical crack-
ing.

Height of the obstacle is 1200 or less

(Unit: mm (inch))

Summary of Contents for MXZ-6C120VA

Page 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Page 2: ...ter space heater stove etc harmful substances will be generated N Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete installation could cause the pipes to burst or injury N When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes If the refriger...

Page 3: ...ear outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Wh...

Page 4: ...t 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the bac...

Page 5: ...outdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Page 6: ...s then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of sto...

Page 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Page 8: ...he live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green Li...

Page 9: ...осы описанные ниже и предназначенные для эксплуатации в жилых помещениях торговых залах и на предприятиях легкой промышленности erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remar...

Reviews: