1-5. INSTALLATION DIAGRAM

Units should be installed by licensed contractor according to local code requirements.

After the leak test, apply insulat-

ing material tightly so that there is 
no gap.

When the piping is to be at-

tached to a wall containing metals 
(tin plated) or metal netting, use 
a chemically treated wooden 
piece 20 mm or thicker between 
the wall and the piping or wrap 7 
to 8 turns of insulation vinyl tape 
around the piping.
To use existing piping, perform 
COOL operation for 30 minutes 
and pump down before removing 
the old air conditioner. Remake 
flare according to the dimension 
for new refrigerant.

ACCESSORIES

Check the following parts before installation.

(1) Drain socket

1

PARTS TO BE PROVIDED AT YOUR SITE

(A) Power supply cord*

1

(B) Indoor/outdoor unit connecting wire*

1

(C) Extension pipe

1

(D) Wall hole cover

1

(E) Piping tape

1

(F)

Extension drain hose 
(or soft PVC hose, 15 mm inner 
diameter or hard PVC pipe VP16)

1

(G) Refrigeration oil

Little 

amount

(H) Putty

1

(I) Pipe fixing band

2 to 7

(J) Fixing screw for (I)

2 to 7

(K) Wall hole sleeve

1

(L)

Soft PVC hose, 15 mm inner di-
ameter or hard PVC pipe VP16 for 
drain socket (1)

1

* Note:

Place indoor/outdoor unit connecting wire (B) and 
power supply cord (A) at least 1 m away from the 
TV antenna wire.

The “Q’ty” for (B) to (K) in the above table is quan-
tity to be used per indoor unit.

More than 
100 mm

Open as a rule
More than 500 mm 
if the front and both 
sides are open

More than 100 mm 
More than 200 mm if there are 
obstacles to both sides

Open as a rule
More than 500 mm if the back, 
both sides and top are open

More than 350 mm

Outdoor unit installation

Air inlet

Air outlet

1-6. DRAIN PIPING FOR OUTDOOR UNIT

Please perform the drain piping work only when draining from one place.
1) Provide drain piping before indoor and outdoor piping connection. 
2) Connect the soft PVC hose (L) I.D.15 mm as shown in the illustration.
3) Make sure to provide drain piping with a downhill grade for easy drain flow.

Note:

Install the unit horizontally.
Do not use the drain socket (1) in the cold regions. Drain may freeze and it makes 
the fan stop. 
The outdoor unit produces condensate during the heating operation. Select the in-
stallation place to ensure to prevent the outdoor unit and/or the grounds from being 
wet by drain water or damaged by frozen drain water.

Air inlet

900 mm

500 mm

200 

mm

2-U-shape notched holes
(Base bolt M10)

320 mm

2 - 12 mm × 36 mm  
oval holes (Base bolt M10)

355 mm

387 mm

(1) Drain socket

(L) Soft PVC hose

Summary of Contents for MXZ-6C120VA

Page 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Page 2: ...ter space heater stove etc harmful substances will be generated N Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete installation could cause the pipes to burst or injury N When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes If the refriger...

Page 3: ...ear outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Wh...

Page 4: ...t 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the bac...

Page 5: ...outdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Page 6: ...s then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of sto...

Page 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Page 8: ...he live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green Li...

Page 9: ...осы описанные ниже и предназначенные для эксплуатации в жилых помещениях торговых залах и на предприятиях легкой промышленности erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remar...

Reviews: